284
APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Status/PUMPSTAT - Pump Status
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Evap Pump #1 Command Off CPUMP_1 Y RW
Evap Pump #2 Command Off CPUMP_2 Y RW
Rotate Evap Pumps ? No ROTCPUMP Y RW
Evap Flow Switch #1 Open FLOW_SW Y RO
Evap Flow Switch #2 Open FLOW_SWB Y RO
Countdown to Rotate hours ROTCNTDN Y RO
Status/RUNTIME - Run Times
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Machine Operating Hours hours HR_MACH Y RO
Machine Starts st_mach N N/A
Compressor A Hours hours HR_CP_A Y RO
Compressor A Starts st_cp_a N N/A
Compressor B Hours hours HR_CP_B Y RO
Compressor B Starts st_cp_b N N/A
Evap Pump #1 Hours hours hr_cpum1 N N/A
Evap Pump #2 Hours hours hr_cpum2 N N/A
VI Cycle Count A Cycles VIctA N N/A
VI Cycle Count B Cycles VIctB N N/A
Circuit A Fan #1 Hours hours hrfana01 N N/A
Circuit A Fan #2 Hours hours hrfana02 N N/A
Circuit A Fan #3 Hours hours hrfana03 N N/A
Circuit A Fan #4 Hours hours hrfana04 N N/A
Circuit A Fan #5 Hours hours hrfana05 N N/A
Circuit A Fan #6 Hours hours hrfana06 N N/A
Circuit A Fan #7 Hours hours hrfana07 N N/A
Circuit A Fan #8 Hours hours hrfana08 N N/A
Circuit A Fan #9 Hours hours hrfana09 N N/A
Circuit A Fan #10 Hours hours hrfana10 N N/A
Circuit A Fan #11 Hours hours hrfana11 N N/A
Circuit A Fan #12 Hours hours hrfana12 N N/A
Circuit A Fan #13 Hours hours hrfana13 N N/A
Circuit A Fan #14 Hours hours hrfana14 N N/A