302
APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Configuration/PUMPCONF
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Evap Pumps Sequence 0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
cpumpseq N N/A
Pump Auto Rotation Delay
Range: 24-3000
Default: 48
hours pump_del
NN/A
NN/A
Pump Sticking Protection No/Yes pump_per N N/A
Flow Checked If Pump Off No/Yes pump_loc N N/A
Configuration/RESETCFG
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Cooling Reset Select 0=None
1=OAT
2=Delta T
3=4 to 20mA control
4=Space Temp
cr_sel N N/A
Cooling NN/A
OAT No Reset Value °F (°C) oat_crno N N/A
OAT Full Reset Value °F (°C) oat_crfu N N/A
Delta T No Reset Value °F (°C) dt_cr_no N N/A
Delta T Full Reset Value °F (°C) dt_cr_fu N N/A
Current No Reset Value mA v_cr_no N N/A
Current Full Reset Value mA v_cr_fu N N/A
Space T No Reset Value °F (°C) spacr_no N N/A
Space T Full Reset Value °F (°C) spacr_fu N N/A
Cooling Reset Deg. Value °F (°C) cr_deg N N/A
Configuration/USER
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
User Password 11=User use_pass N N/A
Service\BACNET
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
BACnet Enable Disabel/Enable bacena N N/A
Metric Unit No/Yes bacunit N N/A
Network Range: 1 to 9999
Default: 1601
network N N/A
Identifier Range: 0 to 9999999
Default: 1600001
ident N N/A
BACnet Management Device 0=None
1=FD(Foreign Device)
2=BBMD(BACnet Broadcast
Management Device)
bbmd N N/A