CL-4
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Record Configuration Information
PATH SmartView™ DESCRIPTION DEFAULT ENTRY
Login Button
Language English
Units US Imp
Main MenuGeneral Parameters Setpoint Select 0 (Auto)
Main MenuConfiguration Menu
General Configuration
Cir Priority Sequence 0 (Auto)
Ramp Loading Enable 0 (No)
Unit Off to On Delay 1 min
Demand Limit Type Select 0 (None)
Night Mode Start Hour 0
Night Mode End Hour 0
Night Capacity Limit 100%
Ice Mode Enable 0 (No)
Main MenuConfiguration Menu
Pump Configuration
Evap Pumps Sequence 0 (No Pump)
Pump Auto Rotation Delay 48 hours
Pump Sticking Protection 0 (No)
Flow Checked If Pump Off 1 (Yes)
Main MenuConfiguration MenuUser Config. User Password 11
Main MenuConfiguration Menu
Reset Configuration
Cooling Reset Select 0 (No reset)
OAT No Reset Value 14° F (–10° C)
OAT Full Reset Value 14° F (–10° C)
Delta T No Reset Value 0 °F (0 °C)
Delta T Full Reset Value 0 °F (0 °C)
Current No Reset Value 0 mA
Current Full Reset Value 0 mA
Space T No Reset Value 14° F (–10° C)
Space T Full Reset Value 14° F (–10° C)
Cooling Reset Deg. Value 0° F (0° C)
Main MenuConfiguration Menu
Factory Parameters
Unit Capacity Unit Dependent
Power Supply Voltage Unit Dependent
Energy Management Module 0
Leakage Charge Detection 0