CL-5
Record Configuration Information
PATH SmartView™ DESCRIPTION DEFAULT ENTRY
Main MenuConfiguration Menu
Service Parameters
Evaporator Fluid Type 1 (Water)
Entering Fluid Control no
Brine Freeze Setpoint 34° F (1.1° C)
Brine Minimum fluid temp 38° F (3.3° C)
Fast Capacity Recovery 0
EWT Probe on cir A side yes
Service Password 88
Leakage Charge Threshold 2.5 Volts
Leakage Charge Timer 60 min.
Compressor RFI Filter En on
Metric Units? no
Send fan drive config? yes
Send comp. Drive config? yes
Evaporator Heater Delta Spt 2 (Number of deg added to brine freeze
setpoint to enable heater)
Freeze override offset 0 °F (0 °C)
Auto Start When SM Lost 0 (disable)
VI Self-Test Threshold 1.15 kW
Pump Rot. AntiFrz Protec on
Main MenuConfiguration Menu
Master Slave Config
Master/Slave Select 0 (disable)
Master Control Type 1 (Local)
Slave Address 2
Lead Lag Select 0 (Always Lead)
Lead/Lag Balance Delta 168 hours
Lead/Lag Start Timer 10 min
Lead Pulldown Time 0 min
Start If Error Higher 4 °F (2.2 °C)
Lag Minimum Running Time 0 min
Lag Unit Pump Control 0 (Stop if Unit Stops)
Chiller In Series 0 (No)
Main MenuSetpoint Table
Cooling Setpoint 1 44° F (6.7° C)
Cooling Setpoint 2 44° F (6.7° C)
Cooling Ice Setpoint 44° F (6.7° C)
Cooling Ramp Loading 1°F (0.6 °C)
Switch Limit Setpoint 1 100%
Switch Limit Setpoint 2 100%
Switch Limit Setpoint 3 100%
LEGEND
Spt —Set Point