18
6 - APPLICATION DATA
6.1 - Operating limits
6.1.1 - 61XWHLZE / 61XWH-ZE units
61XWHZ-E Minimum Maximum
Evaporator
Entering temperature at start-up - Up to 35,0°C
Leaving temperature during operation 3,3°C
(1)
Up to 25,0°C
Condenser
Entering temperature at start-up 13,0°C
(2)
-
Leaving temperature during operation 35,0°C
(2)
Up to 85,0°C
(3)
(1) Use of antifreeze protection is required if the leaving temperature is below 3.3°C
(61XWHLZE range).
(2) For lower condenser temperatures a water ow control valve must be used at
the condenser (two or three-way valve). Please refer to option 152 to ensure
the correct condensing temperature.
(3) Limited to 75°C for model 17
6.1.2 - 61XWHHZE units
Only models 3, 5, 7, 10, 15
61XWHHZE Minimum Maximum
Evaporator
Entering temperature at start-up - Up to 60,0°C
Leaving temperature during operation 20,0°C Up to 55,0°C
Condenser
Entering temperature at start-up 13,0°C
(1)
-
Leaving temperature during operation 35,0°C
(1)
Up to 85°C
(1) For lower condenser temperatures a water ow control valve must be used at
the condenser (two or three-way valve). Please refer to option 152 to ensure
the correct condensing temperature.
Note: Ambient temperatures: During storage and transport
(including by container) the minimum and maximum
permissible temperatures are -20°C and 70°C.
6.2 - Minimum chilled water ow
The minimum chilled water ow is shown in the table in chapter 7.6.
If the system ow is less than the minimum unit ow rate, the
evaporator ow can be recirculated, as shown in the diagram.
For minimum chiller ow rate
1
2
Legend
1 Evaporator
2 Recirculation
6.3 - Maximum chilled water ow
The maximum chilled water flow is limited by the permitted
pressure drop in the evaporator. It is provided in the table in chapter
7.6.
Bypass the evaporator as shown in the diagram to obtain a lower
evaporator ow rate.
For maximum chiller ow rate
Legend
1 Evaporator
2 Recirculation
1
2
6.4 - Condenser water ow rate
The minimum and maximum condenser water ow rates are shown
in the table in chapter 7.6.
6.5 - Standard and optional number of water
passes
The unit is equipped of two passes on evaporator and on
condenser.
61XWH
Model 3 5 7 10 14 15 17
Evaporator
Standard unit 2 2 2 2 2 2 2
Unit with option 100A 3 3 3 3 3 3 3
Unit with option 100C 1 1 1 1 1 1 1
Condenser
Standard unit 2 2 2 2 2 2 2
Unit with option 102A 3 3 3 3 3 3 3
Unit with option 102C 1 1 1 1 1 1 1
6.6 - Evaporator and condenser water ow rates
Units 61XWH
Model 3 5 7 10 14 15 17
Evaporator water ow rate, l/s
Minimum 4 6 8 11 13 13 13
Maximum 39 57 76 84 116 116 116
Condenser water ow rate, l/s
Minimum 4 6 8 12 18 14 14
Maximum 29 55 74 119 130 134 134
Notes :
- Minimum evaporator ow rate based on a water velocity
of 0,3 m/s.
- Minimum condenser ow rate based on a water velocity
of 0,3 m/s.
- Maximum ow rate based on a pressure drop of 120 kPa.
- These values are given for standard units. For options
100A, 100C, 102A and 102C, please refer to the unit
selection program.