29
11 - STANDARD MAINTENANCE
11.5 - Tightening torques for the main bolts and screws
Screw type Used for Torque value, N·m
M20 nut Chassis 190
M20 nut Heat exchanger side-side connection 240
M16 nut Compressor xing 190
H M16 screw Heat exchanger water boxes, structure 190
H M16 screw Compressor suction anges TT 190
H M20 screw Compressor suction anges TU & TV 240
M16 nut Compressor discharge line TT & TU 190
M20 nut Compressor discharge line TV 240
H M12 screw Economiser port ange & economiser port valve, option 92 80
H M8 screw Drier cover 35
1/8 NPT connection Oil line 12
TE nut Compressor oil line 24,5
1 1/16-12 UNF-2A Oil level 130
7/8 ORFS nut Oil line & injection line 130
5/8 ORFS nut Oil line 65
3/8 ORFS nut Oil line 26
H M6 screw Stauff collar 10
Taptite screw M6 Oil line collar 7
Taptite screw M6 Brass body, economiser line 10
Metric screw M6 Steel plate xing, control box, terminal box 7
Taptite screw M10 Oil lter, economiser module, control box xing 30
11.6 - Evaporator and condenser maintenance
Check that:
the insulating foam is intact and securely in place,
the sensors and ow switch are correctly operating and correctly 
positioned in their support,
the water-side connections are clean and show no sign of leakage.
11.7 - Compressor maintenance
11.7.1 - Oil lter change schedule
As system cleanliness is critical to reliable system operation, there
is a lter in the oil line at the oil separator outlet. The oil lter is 
specied to provide a high level of ltration (5 µm) required for 
long compressor life.
The lter should be checked after the rst 500 hours of operation, 
and every subsequent 2000 hours. The lter should be replaced 
at any time when the pressure differential across the lter exceeds 
2 bar.
The pressure drop across the filter can be determined by
measuring the pressure at the discharge port (at the oil separator)
and the oil pressure port (at the compressor).
The difference in these two pressures will be the pressure drop
across the lter, check valve, and solenoid valve. The pressure 
drop across the check valve and solenoid valve is approximately
0.4 bar, which should be subtracted from the two oil pressure
measurements to give the oil lter pressure drop.
11.7.2 - Compressor rotation control
Correct compressor rotation is one of the most critical application
considerations. Reverse rotation, even for a very short duration,
damages the compressor and can even destroy it.
The reverse rotation protection scheme must be capable of
determining the direction of rotation and stopping the compressor
within one second. Reverse rotation is most likely to occur
whenever the wiring at the compressor terminals has been
modied.
To minimise the opportunity for reverse rotation, the following
procedure must be applied. Rewire the power cables to the
compressor terminal pin as originally wired. Apply a counter-torque
at the lower nut at the supply cable terminal during installation.
For replacement of the compressor, a low pressure switch is
included with the compressor. This low pressure switch should be
temporarily installed as a hard safety on the high pressure part of
the compressor. The purpose of this switch is to protect the
compressor against any wiring errors at the compressor terminal
pin. The electrical contact of the switch would be wired in series
with the high pressure switch. The switch will remain in place until
the compressor has been started and direction of rotation has
been veried; at this point, the switch will be removed.
The switch that has been selected for detecting reverse rotation
is Carrier part number HK01CB001. This switch opens the contacts 
when the pressure falls below 7 kPa. The switch is a manual reset
type that can be reset after the pressure has once again risen
above 70 kPa. It is critical that the switch be a manual reset type
to preclude the compressor from short cycling in the reverse
direction
11.8 - Expansion valves maintenance
Replacing of all expansion valves motor is mandatory after 33000
hours of operation.
Maintenance work must be carried out by a trained person fully
qualied  to  work  on  these  units.  Please  contact  your Carrier 
Service representative for information.
NOTE: Any deviation or non-observation of these maintenance
criteria will render the guarantee conditions for the heatpump unit
null and void, and the manufacturer will no longer be held
responsible.