6 - APPLICATION DATA
6.7 - Variable ow evaporator
Variable  evaporator ow can be  used.  The  controlled ow rate 
must  be  higher  than  the  minimum  ow  given  in  the  table  of 
permissible ow rates and must not vary by more than 10% per 
minute.
If the  ow rate changes  more rapidly,  the system should  contain a 
minimum of 6.5 liters of water per kW instead of 3.25 l/kW.
6.8 - System minimum water volume
Whichever the system, the water loop minimum volume is given
by the formula:
Volume = Cap (kW) x N litres
Application N
Normal air conditioning 3,25
Process type cooling 6,5
where Cap is the nominal system heating capacity (kW) at the
nominal operating conditions of the installation.
This volume is necessary for stable operation. It is often necessary
to add a buffer water tank to the circuit in order to achieve the
required volume. The tank must itself be internally bafed in order 
to ensure proper mixing of the liquid (water or brine). Refer to the
examples below.
Conection to buffer tank
Bad Good
Bad
Good