21
7 - WATER CONNECTIONS
ATTENTION: Before carrying out any water connections 
install the water box purge plugs (one plug per water box in 
the lower section supplied in the control box).
For size and position of the heat exchanger water inlet and outlet 
connections refer to the certied dimensional drawings supplied 
with the unit.
The water pipes must not transmit any radial or axial force to the 
heat exchangers nor any vibration.
The  water  supply  must  be  analysed  and  appropriate  ltering, 
treatment, control devices, isolation and bleed valves and circuits 
built in, to prevent corrosion, fouling and deterioration of the pump 
ttings. Consult either a water treatment specialist or appropriate 
literature on the subject.
7.1 - Operating precautions
The water circuit should be designed to have the least number of 
elbows and horizontal pipe runs at different levels. Below the main 
points to be checked for the connection:
• Comply with the water inlet and outlet connections shown 
on the unit.
• Install manual or automatic air purge valves at all high points 
in the circuit(s).
• Use a pressure reducer to maintain pressure in the circuit(s) 
and install a safety valve as well as an expansion tank.
• Install thermometers in both the entering and leaving water 
connections.
• Install drain connections at all low points to allow the whole 
circuit to be drained.
• Install stop valves, close to the entering and leaving water 
connections.
• Use flexible connections to reduce the transmission 
 
of vibrations.
• Insulate all pipework, after testing for leaks, both to reduce 
heat gains and to prevent condensation.
• Cover the insulation with a vapour barrier.
Where  there  are  particles  in  the  uid  that  could foul  the  heat 
exchanger, a screen lter should be installed ahead of the pump. 
The mesh size of the lter must be 1.2 mm.
Before the system start-up verify that the water circuits are 
connected to the appropriate heat exchangers (e.g. no reversal 
between evaporator and condenser). Do not introduce any 
signicant static or dynamic pressure into the heat exchange circuit 
(with regard to the design operating pressures). Before any start-
up  verify  that  the  heat  exchange uid  is  compatible  with the 
materials and the water circuit coating. The use of different metals 
on hydraulic piping could generate eletrolytic pairs and 
consequently  corrosion.  It  could  be  needed  to  add  sacricial 
anodes. In case additives or other uids than those recommended 
by Carrier are used, ensure that the uids are not considered as 
a gas, and that they belong to class 2, as dened in directive 97/23/
EC.
Carrier recommendations on heat exchange uids:
• No NH
4
+
 ammonium ions in the water, they are very 
detrimental for copper. This is one of the most important 
factors for the operating life of copper piping. A content of 
several tenths of mg/l will badly corrode the copper over 
time.
• Cl
-
 Chloride ions are detrimental for copper with a risk of 
perforations by corrosion by puncture. If possible keep 
below 125 mg/l.
• SO
4
2-
 sulphate ions can cause perforating corrosion, if their 
content is above 30 mg/l.
• No uoride ions (<0.1 mg/l).
• No Fe
2+
 and Fe
3+
 ions with non negligible levels of dissolved 
oxygen must be present. Dissolved iron < 5 mg/l with 
dissolved oxygen < 5 mg/l.
• Dissolved silicon: silicon is an acid element of water and 
can also lead to corrosion risks. Content < 1 mg/l.
• Water hardness: > 0.5 mmol/l. Values between 1 and 2.5 can 
be recommended. This will facilitate scale deposit that can 
limit corrosion of copper. Values that are too high can cause 
piping blockage over time. A total alkalimetric titre (TAC) 
below 100 mg/l is desirable.
• Dissolved oxygen: Any sudden change in water oxygenation 
conditions must be avoided. It is as detrimental to deoxygenate 
the water by mixing it with inert gas as it is to over-oxygenate it 
by mixing it with pure oxygen. The disturbance of the oxygenation 
conditions encourages destabilisation of copper hydroxides and 
enlargement of particles
.
• Electric conductivity 10-600µS/cm.
• pH: Ideal case pH neutral at 20-25°C 7 < pH < 8
When the water circuit must be emptied for longer than one month 
or immediately if the water does not comply with the above 
description, the circuit must be either totally dried or placed under 
0.5 bar maximum nitrogen charge. This is done to avoid any 
damage of the exchanger copper tubes with corrosion by 
differential aeration. In case of nitrogen charge, the circuit must 
be equipped with relief valves to avoid overpressure due to 
refrigerant leakage. Charging and removing heat exchange uids 
should be done with devices that must be included on the water 
circuit by the installer. Never use the unit heat exchangers to add 
heat exchange uid.
CAUTION: Filling, completing and draining the water circuit 
charge must be done by qualied personnel, using the  air 
purges and materials that are suitable for the products.
Charging and removing heat exchange uids should be done 
with devices that must be included on the water circuit by the 
installer.  Never  use  the unit  heat  exchangers  to  add  heat 
exchange uid. 
7.2 - Water connections
The water connections are Victaulic type connections. The inlet 
and outlet connection diameters are identical.
Inlet/outlet diameters
61XWH
Model 3 5 7 10 14 15 17
Evaporator
Standard unit
Nominal diameter in 5 6 8 8 8 8 8
Actual outside diameter mm 141,3 168,3 219,1 219,1 219,1 219,1 219,1
Unit with option 100A
Nominal diameter in 4 5 6 6 6 6 6
Actual outside diameter mm 114,3 141,3 168,3 168,3 168,3 168,3 168,3
Unit with option 100C
Nominal diameter in 5 6 8 8 8 8 8
Actual outside diameter mm 141,3 168,3 219,1 219,1 219,1 219,1 219,1
Condenser 
Standard unit
Nominal diameter in 5 6 8 8 8 8 8
Actual outside diameter mm 141,3 168,3 219,1 219,1 219,1 219,1 219,1
Unit with option 102A
Nominal diameter in 4 5 6 6 6 8 8
Actual outside diameter mm 114,3 141,3 168,3 168,3 168,3 219,1 219,1
Unit with option 102C
Nominal diameter in 6 8 8 8 8 8 8
Actual outside diameter mm 168,3 219,1 219,1 219,1 219,1 219,1 219,1