EasyManua.ls Logo

Carrier CAS072 - Appendix A - Air Conditioner and Heat Pump with R-410 A - Quick Reference Guide; Appendix B - Wiring Diagrams

Carrier CAS072
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAS-072-153-01SI Rev. A Specifications subject to change without notice. 35
APPENDIX A — AIR CONDITIONER AND HEAT PUMP WITH R-410A –
QUICK REFERENCE GUIDE
• R-410A refrigerant operates at 50 percent to 70 per-
cent higher pressures than R-22. Be sure that servic-
ing equipment and replacement components are de-
signed to operate with R-410A refrigerant.
• R-410A refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be
400 psig, DOT 4BA400 or DOT BW400.
• R-410A systems should be charged with liquid refrig-
erant. Use a commercial type metering device in the
manifold hose when charging into suction line with
compressor operating.
• Manifold sets should be 700 psig high side and
180 psig low side with 550 psig low-side retard.
• Use hoses with 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC
refrigerant.
• R-410A, as with other HFCs, is only compatible with
POE oils.
• Vacuum pumps will not remove moisture from oil.
• Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
• Do not install a suction-line filter drier in liquid-line.
• POE oils absorb moisture rapidly. Do not expose oil
to atmosphere.
• POE oils may cause damage to certain plastics and
roofing materials.
• Wrap all filter driers and service valves with wet cloth
when brazing.
• A factory approved, liquid-line filter drier is required
on every unit.
• Do not use an R-22 TXV.
• If indoor unit is equipped with a TXV, it must be
changed to an R-410A TXV.
• Never open system to atmosphere while it is under a
vacuum.
• When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
• Always replace filter drier after opening system for
service.
• Do not vent R-410A refrigerant into the atmosphere.
• Do not use capillary tube coils.
• Observe all warnings, cautions, and bold text.
• All R-410A heat pumps must have indoor TXV.
• Do not leave R-410A suction line driers in place for
more than 72 hours.
APPENDIX B — WIRING DIAGRAMS
UNIT
ELECTRICAL
CHARACTERISTICS
DIAGRAM NUMBER PAGE NUMBER
CAS072
208/230-3-60 38AU000441 36
460-3-60 38AU000441 36
575-3-60 38AU000442 37
CAS091
208/230-3-60 38AU000759 38
460-3-60 38AU000760 39
575-3-60 38AU000758 40
CAS121
208/230-3-60 38AU501323 41
460-3-60 38AU501322 42
575-3-60 38AU501324 43
CAS151
208/230-3-60 38AU501326 44
460-3-60 38AU501325 45
575-3-60 38AU501327 46
CAS123
208/230-3-60 38AU501320 47
460-3-60 38AU501319 48
575-3-60 38AU501321 49
CAS153
208/230-3-60 38AU501320 47
460-3-60 38AU501319 48
575-3-60 38AU501321 49