6 - CONFIGURING THE UNIT
Access level No. Description Setting By default Display condition
LOCKING
2 99 Locking of the conguration
0: Conguration unlocked
(The unit cannot be started up; the unit type
parameters may be changed).
1: Conguration locked
(The unit can be started up by pressing the
"On/O" push button on the console. The
unit type parameters may no longer be
modified. The number of times the
conguration is unlocked is counted.)
0
(*) When these parameters are modied, a sequence is launched to congure the FMAs.
6.1.2 - CONTROL AND SETTINGS (sub-menu 3.2)
Access level No. Description Setting By default Display condition
1 100 Language used
0: French
1: English
2: German
3: Spanish
0
1 101 Date Day/Month/Year
1 102 Time Hours/Minutes
COOLING CONTROL
1 103
Temperature setpoint in cooling
mode
8,0 to 45,0 °C if P08 = 0
MAX (10, P106) to 45,0 °C if P08 > 0
25,0 °C P07 > 0
1 104
Temperature proportional band
in cooling mode
1,0 to 10,0 K 2,0 K P07 > 0
1 105
Temperature integral time in
cooling mode
0 min 0 s to 30 min 0 s (0 to 1800 s) 0 min 0 s P07 > 0
HEATING CONTROL
1 106
Temperature setpoint in heating
mode
10,0 to 35,0 °C
10,0 to MIN (35,0, P103) °C
20,0 °C P08 > 0
1 107
Temperature proportional band
in heating mode
1,0 to 10,0 K 2,0 K P08 > 0
1 108
Integral time Temperature in
heating mode
0 min 0 s to 30 min 0 s (0 to 1800 s) 0 min 0 s P08 > 0
DEHUMIDIFICATION CONTROL
1 109
Humidity setpoint during
dehumidication
20 to 90% if P10 = 0
MAX (20, P115) to 90 % if P10 > 0
60% P09 > 0
1 110
Humidity proportional band in
dehumidication mode
5 to 30% 10% P09 > 0
1 111
Humidity integral time in
dehumidication mode
0 min 0 s to 30 min 0 s (0 to 1800 s) 0 min 0 s P09 > 0
HUMIDIFICATION CONTROL
1 115
Humidity setpoint during
humidication
20 to 90% if P09 = 0
MAX (20, P109) to 90 % if P09 > 0
40% P10 > 0
1 116
Humidity proportional band in
humidication mode
5 to 30% 10% P10 > 0
1 117
Humidity integral time in
humidication mode
0 min 0 s to 30 min 0 s (0 to 1800 s) 0 min 0 s P10 > 0
RETURN TEMPERATURE LIMITATION
1 121
Downward shift of the
temperature limit
0,0 to 10,0 K 2 K P06 = 0 and P09 > 0
1 122
Proportional band for reduction
of the cooling demand
1,0 to 10 K 2 K P06 = 0 and P09 > 0