Carrier DesertMaster 50TJM
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RLA LRA RLA LRA Qty HP FLA HP FLA
Appl.
KW
FLA
360 440 400 / 3 / 50
12.2 101 12.2 101 2 1 3.4 Std. Eff. 4 6.3
- -
40.6 50
360 440 400 / 3 / 50
12.2 101 12.2 101 2 1 3.4 High Eff. 4 6.15 - - 40.4 50
360 440 400 / 3 / 50
12.2 101 12.2 101 2 1 3.4 Std. Eff. 4 6.3 21 30.3 44.2 50
360 440 400 / 3 / 50
12.2 101 12.2 101 2 1 3.4 High Eff. 4 6.15 21 30.3 44.0 50
360 440 400 / 3 / 50
16.7 111 16.7 111 2 1 3.4 Std. Eff. 5.5 8.3 - - 52.7 60
360 440 400 / 3 / 50
16.7 111 16.7 111 2 1 3.4 High Eff. 5.5 8 - - 52.4 60
360 440 400 / 3 / 50
16.7 111 16.7 111 2 1 3.4 Std. Eff. 5.5 8.3 28 40.4 58.8 90
360 440 400 / 3 / 50
16.7 111 16.7 111 2 1 3.4 High Eff. 5.5 8 28 40.4 58.5 90
360 440 400 / 3 / 50
17.9 118 17.9 118 2 1 3 Std. Eff. 5.5 8.3
- -
57.6 70
360 440 400 / 3 / 50
17.9 118 17.9 118 2 1 3 High Eff. 5.5 8 - - 57.3 70
360 440 400 / 3 / 50
17.9 118 17.9 118 2 1 3 Std. Eff. 5.5 8.3 28 40.4 61.8 100
360 440 400 / 3 / 50
17.9 118 17.9 118 2 1 3 High Eff. 5.5 8 28 40.4 61.5 100
360 440 400 / 3 / 50
21.8 140 21.8 140 2 1 3 Std. Eff. 7.5 11.3 - - 66.4 80
360 440 400 / 3 / 50
21.8 140 21.8 140 2 1 3 High Eff. 7.5 11
- -
66.1 80
360 440 400 / 3 / 50
21.8 140 21.8 140 2 1 3 Std. Eff. 7.5 11.3
28 40.4
66.4 100
360 440 400 / 3 / 50
21.8 140 21.8 140 2 1 3 High Eff. 7.5 11
28 40.4
66.1 100
Legend and Notes for Electrical Data Table
HACR - Heating, Air-Conditioning and Refrigeration
AB = 392v
BC = 404v
AC = 395v
1191
3
(AB) 397 - 392 =5v
(BC) 404 - 397 =7v
(AC) 457 - 397 =2v
7
397
MCA MOCP◊
18
50TJM Size 18 - 34 Compressor
OFM
IFM Type
Unit Size
50TJM
Min Voltage
Max
Voltage
Power
Supply
V / Ph / Hz
No.1 No.2
Determine Percentage Voltage Imbalance.
FLA - Full Load Amps
= 100 X
IFM -
Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
Maximum Deviation is 7v.
Unbalanced 3-Phase Supply Voltage
=
Average Voltage =
Use the following formula to determine the percentage of voltage imbalance
* Application heater kW @ 400 volt (Using multiplication factor table in Electric Resistance Heater Data table on page 13)
3
Electrical Data Table - 3
24
28
34
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
NEC - National Electrical Code
IFM
Electric
Heater
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
OFM -
Outdoor (Condenser) Fan Motor
RLA - Rated Load Amps
MCA - Minimum Circuit Amps
MOCP -
Maximum Overcurrent Protection
Example: Supply Voltage is 400V - 3ph - 50Hz
Maximum Deviation From Average Voltage
Average Voltage
◊ Fuse or HACR Circuit Breaker
= 100 X
% Voltage Imbalance
Determine maximum deviation from average voltage.
= 397V
= 1.76%
392 + 404 + 395
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
Page 11