Fan Performance Table - 7 (cont)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000 535 1.06 1.21 592 1.27 1.45 647 1.50 1.71 700 1.75 2.00 753 2.02 2.31
5500 564 1.30 1.49 618 1.53 1.75 669 1.77 2.03 718 2.03 2.32 766 2.29 2.62
6000 596 1.59 1.82 643 1.82 2.09 692 2.07 2.37 738 2.34 2.68 783 2.63 3.01
6500 625 1.92 2.19 671 2.16 2.47 715 2.43 2.78 759 2.70 3.09 801 2.99 3.43
7000 656 2.28 2.61 698 2.54 2.91 740 2.82 3.22 781 3.10 3.55 821 3.40 3.89
7500 686 2.70 3.09 726 2.97 3.40 766 3.26 3.73 804 3.55 4.06 843 3.86 4.42
8000 714 3.15 3.61 753 3.43 3.93 790 3.74 4.28 827 4.04 4.63 864 4.37 5.00
8500 743 3.64 4.17 779 3.94
4.51 815 4.25 4.87 849 4.56 5.22 884 4.89 5.60
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000 801 2.30 2.64 849 2.61 2.98 898 2.93 3.36 944 3.28 3.75 989 3.64 4.17
5500 813 2.60 2.97 859 2.90 3.32 904 3.23 3.70 948 3.58 4.10 990 3.94 4.51
6000 827 2.93 3.36 870 3.23 3.70 913 3.57 4.09 955 3.92 4.48 996 4.28 4.90
6500 843 3.30 3.77 884 3.62 4.15 924 3.96 4.53 964 4.30 4.93 1002 4.67 5.34
7000 861 3.72 4.25 900 4.05 4.64 939 4.39 5.02 976 4.74 5.43 1013 5.11 5.85
7500 880 4.19 4.79 917 4.52 5.18 954 4.87 5.57 989 5.22 5.98 1025 5.60 6.41
8000 899 4.69 5.37 935 5.04 5.76 969 5.39 6.17 1004 5.76 6.59
1038 6.14 7.03
8500 919 5.23 5.99 952 5.59 6.40 985 5.96 6.82 1017 6.32 7.24 1051 6.71 7.68
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000
535 1.02 1.21 592 1.22 1.45 647 1.44 1.71 700 1.69 2.00
753 1.95 2.31
5500 564 1.25 1.49 618 1.47 1.75 669 1.71 2.02 718 1.96 2.32 766 2.21 2.62
6000 596 1.53 1.82 643 1.76 2.08 692 2.00 2.37 738 2.26 2.68 783 2.53 3.01
6500 625 1.85 2.19 671 2.08 2.47 715 2.34 2.78 759 2.60 3.09 801 2.89 3.43
7000 656 2.20 2.61 698 2.45 2.91 740 2.71 3.22 781 2.99 3.55 821 3.28 3.89
7500 686 2.60 3.09 726 2.87 3.40 766 3.14 3.73 804 3.42 4.06 843 3.72 4.42
8000 714 3.04 3.61 753 3.31 3.93 790 3.60 4.28 827 3.90 4.62 864 4.21 5.00
8500 743 3.51 4.17 779 3.79 4.50 815 4.10 4.86 849 4.40 5.22 884 4.71 5.60
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
5000 801 2.22 2.64 849 2.51 2.98
898 2.83 3.35 944 3.16 3.75 989 3.51 4.17
5500 813 2.50 2.97 859 2.80 3.32 904 3.12 3.70 948 3.45 4.10 990 3.79 4.50
6000 827 2.83 3.35 870 3.12 3.70 913 3.44 4.09 955 3.77 4.48 996 4.13 4.90
6500 843 3.18 3.77 884 3.49 4.15 924 3.81 4.53 964 4.15 4.92 1002 4.50 5.34
7000 861 3.58 4.25 900 3.91 4.64 939 4.23 5.02 976 4.57 5.43 1013 4.92 5.85
7500 880 4.04 4.79 917 4.36 5.18 954 4.69 5.57 989 5.04 5.98 1025 5.40 6.41
8000 899 4.52 5.37 935 4.85 5.76 969 5.20 6.17 1004 5.55 6.59 1038 5.92 7.03
8500 919 5.05 5.99 952 5.39 6.40 985 5.74 6.82 1017 6.10 7.24 1051 6.47 7.68
8. Conversion - Bhp to KWI
Air Flow Rate
(CFM)
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
0.2 0.4
0.4
1.8
Legend:
RPM - Revolutions Per Minute
Bold, Italics - Standard Motor and Drive Package
0.6 0.8 1.0
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor)
KWI=
Bhp X 0.746
Motor efficiency
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor)
0.6 0.8 1.0
1.2
1.4
1.6
2.0
0.2
Bold , Italics - High Efficiency Motor and Drive Package
Air Flow Rate
(CFM)
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor) (cont)
1.2
1.4
1.6
1.8
2.0
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Page 22