EasyManua.ls Logo

Carrier EVERGREEN 30HXA - Page 4

Carrier EVERGREEN 30HXA
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Fig. 4 — Dimensions, 30HXC161-186
NOTES:
1. Operating weight includes weight of
water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are in inches (mm).
4. Recommended service clearance
around machine is 36 in. (914.4 mm).
5. Victaulic nozzles are standard on all
models. Flow switch factory installed
in cooler outlet victaulic nozzle.
UNIT
OPERATING
WEIGHT - lb (kg)
BC
WGT DISTRIBUTION AT EACH
MTG PLATE - lb (kg)
123456
30HXC161
7452
(3381)
72.12
(1832)
50.63
(1286)
817
(371)
1272
(577)
908
(412)
1219
(553)
1890
(857)
1346
(610)
30HXC171
7660
(3475)
61.37
(1559)
61.37
(1559)
936
(425)
1318
(598)
840
(381)
1379
(626)
1946
(883)
1241
(563)
30HXC186
7854
(3564)
61.37
(1559)
61.37
(1559)
962
(436)
1361
(617)
860
(390)
1410
(640)
1996
(905)
1265
(574)
a30-4649

Related product manuals