5
NOTES:
1. Operating weight includes weight of water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are in inches (mm).
4. Recommended service clearance around machine is 36 in. (914.4 mm).
5. Victaulic nozzles are standard on all models. Flow switch factory installed
in cooler outlet victaulic nozzle.
UNIT
OPERATING
WEIGHT - lb (kg)
A
WGT DISTRIBUTION AT EACH
MTG PLATE - lb (kg)
123456
30HXC206
10,581
(4799)
33.88
(860)
948
(430)
2406
(1091)
1243
(564)
1201
(545)
3133
(1421)
1650
(748)
30HXC246
10,969
(4976)
34.38
(873)
985
(447)
2515
(1141)
1306
(592)
1154
(523)
3276
(1486)
1733
(786)
30HXC261
10,992
(4986)
34.38
(873)
985
(447)
2520
(1143)
1311
(595)
1154
(523)
3283
(1489)
1739
(789)
30HXC271
11,029
(5003)
34.38
(873)
985
(447)
2529
(1147)
1318
(598)
1154
(523)
3294
(1494)
1749
(793)
Fig. 5 — Dimensions, 30HXC206-271