i-Vu® XT Router (drv_gen5) CARRIER CORPORATION ©2022
Installation and Start-up Guide 21 All rights reserved
Identification
Auto Name Scheme
Not Autogeneratedyou can enter a specific name that is unique on the
network.
Autogeneratedthe Device Name is automatically set as the word "device +
the Device Instance". For example, "device2423911". You cannot edit the
field.
Device Name
Contents and editability depend on your Auto Name Scheme choice.
Location
You can enter an intuitive location for the device in the i-Vu® interface. This will
be the device's display name when discovered through Find Devices.
Description
You can enter an intuitive description for the device in the i-Vu® interface.
Vendor Name
This is autogenerated based on the BACnet vendor ID. It is hardcoded in the
firmware and not editable.
Vendor Identifier
This is autogenerated based on the BACnet vendor ID. It is hardcoded in the
firmware and not editable.
Firmware Revision
The firmware version that is in the BACnet device.
APDU
The following three fields refer to all networks over which the i-Vu® XT Router communicates.
APDU Timeout
How many milliseconds the device will wait before resending a message if no
response is received.
APDU Segment Timeout
How many milliseconds the device will wait before resending a message segment
if no response is received.
Number of APDU Retries
The number of times the device will resend a message.
Gig-E Port using BACnet/IPv4
Primary BACnet/IP
Home network
or
Set as home
This is typically the network that is communicating with the building automation
system's application. This sets the BACnet Address of the Device Object. If the
port is Enabled, the user can set this port as the home network to identify it as
the connection to the i-Vu® application.
Click Disable if you want to disable the port from use.
Auto Generate Network
Number
If checked, network number is autogenerated, which then automatically sets to
((IP network number + rotary switch address) x 10) + 0.
Uncheck to use Custom Static Address Mode.
Network Number
Specify a number for the BACnet/IP network or set to 0 if the port is not used.
The network number is 0 by default. Filled in automatically if Autogenerate
Network Number is checked.
NOTE When downloaded from the i-Vu® application, these numbers match those
set using SiteBuilder.