25TPB7: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
Check Defrost Thermostat
Check  defrost  thermostat  to  ensure  it  is  properly  located  and  securely
attached.  There  is  a  liquid  header  with  a  distributor  and  feeder  tube
going into outdoor coil. At the end of the one of the feeder tubes, there is
a  3/8  in.  O.D.  stub  tube  approximately  2  in.  long.  (See  Fig. 3.)  The
defrost thermostat should be located on stub tube. Note that there is only
one stub tube used with liquid header, and on most units it is the bottom
circuit. 
A97517
Fig. 3 – Defrost Thermostat Location
Elevate Unit
Elevate  unit  per  local  climate  and  code  requirements  to  provide
clearance above estimated snowfall level and ensure adequate drainage
of unit. 
In Long-Line Applications, Install Liquid-Line 
Solenoid Valve (LSV)
For refrigerant piping arrangements with equivalent lengths greater than
80  ft.  (24  m)  and/or  when  elevation  difference  between  indoor  and
outdoor unit is greater than ±20 ft. (±6.1 m), follow all requirements of
the  Residential  Piping  and  Long-Line  Guideline.  If  required  by
Long-Line  Guideline,  install  LSV  kit,  part  no.  KHALS0401LLS,
specifically designed for R-410A refrigerant heat pumps. LSV should be
installed within 2 ft.  (0.6 m) of  outdoor unit with  flow  arrow pointing
toward outdoor unit. Follow the  Installation Instructions included with
accessory kit. 
IMPORTANT: Flow arrow must point toward outdoor unit. 
Make Piping Connections
Outdoor  units  may  be  connected  to  indoor  section  using  accessory
tubing package or field-supplied refrigerant grade tubing of correct size
and condition. For tubing requirements beyond 80 ft (24 m), substantial
capacity  and  performance  losses  can  occur.  Following  the
recommendations  in  the  Residential  Piping  and  Long  Line  Guideline
will  reduce these losses.   Refer to  Table 1 for  accessory  requirements.
Refer to Table 2 for field tubing diameters.
There are no buried-line applications greater than 36 in. (914 mm)
If refrigerant tubes or indoor coil are exposed to atmosphere, they must
be evacuated to 500 microns to eliminate contamination and moisture in
the system.
Outdoor Unit Connected to Factory Approved Indoor 
Unit:
Outdoor  unit  contains  approximate  system  refrigerant  charge  for
operation with approved AHRI rated indoor unit when connected by 15ft
(4.6  m)  of  field–supplied  or  factory–accessory  tubing,  and  factory
supplied filter drier. Check refrigerant charge for maximum efficiency.
Service Valves
Service valves  are closed and  plugged from the factory. Outdoor  units
are shipped with a refrigerant charge sealed in the unit. Leave the service
valves closed until all other refrigerant system work is complete or the
charge will be lost. Leave the plugs in place until line set tubing is ready
to be inserted.
Heat pumps require a piston metering device in the liquid service valve
for proper heating operation. Piston is shipped in the piston body of the
liquid service valve, temporarily held in place with a plastic cap. Do not
remove the plastic cap until line set tubing is ready to be installed.
Refer to Fig. 4 and follow these steps for piston installation:
1. Remove plastic cap holding piston in piston body of liquid service
valve.
2. Check  that  piston  size  (stamped  on  side  of  piston)  matches  with
number listed on unit rating plate. Return piston to piston body of
liquid service valve (either direction).
3. Find plastic bag taped to unit containing copper adapter tube, brass
nut, and plastic washer.
4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install  tube onto liquid service
valve. Tighten nut finger tight, then wrench additional ½ turn only
[15-ft  lbs  (20  N-m)].  Over  tightening  may  damage  the  plastic
washer and service valve’s piston body.
A14235
Fig. 4 – Liquid Service Valve with Heating Piston and Adapter Tube
CAUTION
!
UNIT OPERATION HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Do not allow water and/or ice to build up in base pan.
WARNING
!
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve  pressure  and  recover  all  refrigerant  before  system  repair  or
final unit disposal. 
Use  all  service  ports  and  open  all  flow-control  devices,  including
solenoid valves.
Federal  regulations  require  that  you  do  not  vent  refrigerant  into  the
atmosphere.    Recover  refrigerant  during  system  repair  or  final  unit
disposal
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
If ANY refrigerant tubing is buried, provide a 6-in (152 mm). vertical
rise at service valve.  Refrigerant tubing lengths up to 36-in  (914 mm).
may be buried without further special consideration.  Do not bury lines
longer than 36 in (914 mm).