Installation manual
Please select power supply for indoor unit and outdoor unit 
separately.
The power supply should have  specified branch circuit with 
leakage protector and manual switch.
The power supply, leakage protector and manual of all the 
indoor units connecting to the same outdoor unit should be 
universal. (Please set all the indoor unit power supply of 
one system into the same circuit. It should turn on or shut 
down the unit at the same time, otherwise, the service life 
would affect seriously, even the unit may not turn on.) 
Please put the connective wiring system between indoor 
unit and outdoor unit with refrigerant piping system together.
It is suggested to use 3-core shielded wire as signal wire 
between indoor and outdoor units, multi-core wire is 
unavailable.
Please comply with relevant National Electric Standard.
Power wiring should be done by professional electrician.
CAUTION
6.5  Electric wiring system and installation
Separate Power Supply (without power facility)  (See 
Table.6-3)
With power facilities 
Outdoor unit 
power supply
Leakage 
protector
Manual 
 switch 
Outdoor unit 
Outdoor unit 
Outdoor unit 
Outdoor unit 
GND
GND
GND
GND
Branch box
Leakage 
protector
Manual 
 switch 
380-415V 3N~ 50Hz
Fig.6-5
Fig.6-6
NOTE
Select power cord for these five models separately according 
to relevant standard. 8HP, 10HP, 12HP, 14HP16HP18HP
The  wiring diameter and the length in the table indicate the 
condition that the voltage dropping range is within 2%. If the 
length exceeds the above figure, please select the wire 
diameter according to relevant standard.
Table.6-3
Power 
supply
Leakage 
protector
           Size
(Continuous length
   of pipe m)
Capacity 
Fuse 
Grounding 
    wire
Model
Item
 Min. Power wire diameter (mm
2
) 
Wiring of mental and synthetic resin
 Manual switch 
          (A)
       8HP
380-415V
3N~ 50Hz
100mA
0.1sec or 
    less
   12HP
4×10 mm
2 
(<20 m)
4×16 mm
2 
(<50 m)
4×10 mm
2 
(<20 m)
4×16 mm
2 
(<50 m)
1×10 mm
2
1×10 mm
2
50
40
32
25
Leakage 
protector
Manual 
 switch 
GND
Branch box
Outdoor unit 
GND
Outdoor unit 
GND
Outdoor unit 
GND
Outdoor unit 
GND
Outdoor unit 
GND
Outdoor unit 
6.5.1  Outdoor unit power wiring
E
D
     Power facilities 1
(with leakage protector)
     Power facilities 2
(with leakage protector)
D
Select the wire diameter
Power wiring refer to the main wire (a) connecting to branch 
box and the wiring (b) between branch  box and power 
facilities. Please select the wire diameter according to the 
following requirement.
Diameter of main wire (a)
Depends on the total horsepower of outdoor unit and 
following table.
E.g In system:(8Hp×1unit+8Hp×1unit+10Hp×1unit) 
Total Hp=26Hp→(Table.6-4)→size of wire=35mm
2
(within 
50m)
Wiring(b):between branch box and power equipment. 
Depends on the number of combined outdoor unit. If fewer 
than 5, the diameter is the same as that of main wire (a); if 
more than 6, there will be 2 electric control boxes, and the 
diameter of wiring depends on the total horsepower of  
outdoor units connecting to each electric control box and 
following table.
Select wire diameter (≥) (table.6-4)   (unit :mm
2
)  
   14HP
   16ǃ18HP
4×16 mm
2 
(<20 m)
4×25 mm
2 
(<50 m)
1×16mm
2
50
40
4×16 mm
2 
(<20 m)
4×25 mm
2 
(<50 m)
1×16mm
2
63 50