Table.6-4
Select the capacity of manual switch and fuse of the branch 
box.
See following table when without power facilities, depends on 
the outdoor unit it connecting to. 
See table.6-5 below when there is power facility, depends on 
the total horsepower.
Indoor power supply
Indoor power
Leakage protector
Manual switch
Branch box
Indoor unit
Fig.6-7
Set refrigerant piping system, signal wires between 
indoor-indoor unit, and that between outdoor-outdoor unit 
into one system. 
Power must unified supply to all indoor units in the same 
system.
Please do not put the signal wire and power wire in the 
same wire tube; keep distance between the two tubes. 
(Current capacity of power supply: less than 10A--300mm, 
less than 50A--500mm.)
Make sure to set address of outdoor unit in case of parallel 
multi-outdoor units.
CAUTION
Table.6-5
Total horsepower, capacity of manual switch and fuse 
Total (HP)
   Manual switch (A)
Fuse(A)
     8
12~14
16~18
20~22
24~28
30~34
32
50
63
80
 90
100
25
40
50
63
  70
  80
Total (HP)
   Manual switch (A)
Fuse(A)
36~40
42~44
46~50
52~60
62~72
110
125
150
200
 250
 90
100
125
150
200
90
110
66
90
110
68
90
110
70
90
110
72