No. Status  Unit  
1 0 to 4 0 - Cooling Reset Select Cooling reset selection
2 0 to 4 0 - Heating Reset Select Heating reset selection
3 0 = None, 1 = OAT 0 = none, 1 = outdoor temperature
4 2 = Delta T, 4 = Space Temp 2 = delta T, 4 = space temperature
5 3 = 4-20 mA control 3 = 4-20 mA control
6
7 Cooling Cooling mode
8 -10.0 to 51.7 -10 °C OAT No Reset Value Outdoor temperature, no reset
9 -10.0 to 51.7 -10 °C OAT Full Reset Value Outdoor temperature, max. reset
10 0 to 13.9 0 ^C Delta T No Reset Value Delta T, no reset
11 0 to 13.9 0 ^C Delta T Full Reset Value Delta T, max. reset
12 0 to 20 0 mA Current No Reset Value Current, no reset
13 0 to 20 0 mA Current Full Reset Value Current, max. reset
14 -10.0 to 51.7 -10 °C Space T No Reset Value Space temperature, no reset
15 -10.0 to 51.7 -10 °C Space T Full Reset Value Space temperature, max. reset
16 -30 to 30 0 ^C Cooling Reset Deg. Value Maximum cooling reset value
17
18 Heating Heating mode
19 -10.0 to 51.7 -10 °C OAT No Reset Value Outdoor temperature, no reset
20 -10.0 to 51.7 -10 °C OAT Full Reset Value Outdoor temperature, max. reset
21 0 to 13.9 0 ^C Delta T No Reset Value Delta T, no reset
22 0 to 13.9 0 ^C Delta T Full Reset Value Delta T, max. reset
23 0 to 20 0 mA Current No Reset Value Current, no reset
24 0 to 20 0 mA Current Full Reset Value Current, max. reset
25 -10.0 to 51.7 -10 °C Space T No Reset Value Space temperature, no reset
26 -10.0 to 51.7 -10 °C Space T Full Reset Value Space temperature, max. reset
27 -16.7 to 16.7 0 ^C Heating Reset Deg. Value Maximum heating reset value

Name  Units 
d_of_m 1 to 31 - Day of the month
month 1 to 12 - Month
year 0 to 99 - Year
dow 1 to 7 - Day of the week
hour 0 to 24 h Hour
minutes 0 to 59 min Minutes
dlig_o yes/no - Winter time change-over active?
tod_hol yes/no - Holiday today?
tom_hol yes/no - Holiday tomorrow?

Name  
elemt_nb 1 to 239 Element number
bus_nb 0 to 239 Bus number
baudrate 9600 to 38400 Communication speed
30XWV Touch Pilot Device description
--------------------- Location description
CSA-SR-20M49010 Software number
--------------------- Serial number
* Depends on selected language, default is English

No. Status  Unit  
1 1 to 9999 11 - User Password User password