99 | P a g e
2) During the Guided Setup process you will be asked the following three questions:
a. Press Yes
b. Press Yes
c. Press Dehumidifier
NOTE: The DHUM on furnace board is active in the open state. The ACC+
terminal for dehumidifiers is defaulted to active open. So, no other changes are
necessary. You can double check this setting on the thermostat
Menu > (hold) Service > Installation Settings > Equipment Setup >
Accessory > Dehum Open
3) Complete the Guided Setup installation process.
4) (Optional) Configure Cool to Dehumify
a. Select Menu > Profiles > Humidity Profiles > Dehumidification Setpoint
b. Default: Disabled
c. Options: Overcool temperature between 0.5oF and 5oF or disabled
Humidity setpoint between 46% and 58%