95 | P a g e
Ideal Humidity System
®
Technology with Infinity
®
Furnaces
Infinity
®
units are capable of full Ideal Humidity System
®
Technology which includes
Super Dehumidification.
1) Dehumidification: When there is a call for cooling and a call for dehumidification,
the furnace delivers airflow which is 86% of the nominal cooling.
2) Super Dehumidification: When there is a demand for dehumidification without a
demand for cooling, the furnace will run at 65% of the nominal cooling speed for
a maximum of 10 min per cycle. After 10 min, the furnace blower speed will
revert back to the dehumidification speed of 86%. Normal staging algorithms
between low-stage and high-stage cooling are applied during super-
dehumidification. Super dehumidification setting automatically over cools up to
3
o
F.
3) SmartEvap: The blower will shut down within 5 seconds after a cooling to
prevent re-evaporation of the water on the coil.
NOTE: When Super Dehumidification is enabled, this feature cannot be
overridden by changing the Cool to Dehumidify to 0
o
F.
Set Up Ideal Humidity System® Technology on an Infinity® Furnace
1) ACC+ should be connected to the DH terminal on the furnace control. Nothing
will be connected to ACC-.
2) During the Guided Setup process you will be asked the following three questions:
a. Press Yes

Table of Contents