8--2
T--311
CLOSE- UP VIEW
COIL FINS
Figure 1-11 Micro-Channel Style Condenser Assembly
Table 8-2 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (GEN--5)
Evaporator
GEN 5
Condenser
All Series
Recommended
R134a Charge
Recommended
Oil Charge*
GEN 5 - EM-1 CM-2 or CM-4 4.75 Pounds 9.5 Ounces
GEN 5 - EM-1 CM-11 5.00 Pounds 10.0 Ounces
GEN 5 - EM-1 CM-3 5.25 Pounds 10.5 Ounces
GEN 5 - EM-1 CM-7 6.25 Pounds 12.5 Ounces
GEN 5 - EM-7 CM-2 or CM-4 4.00 Pounds 8.0 Ounces
GEN 5 - EM-7 CM-11 4.25 Pounds 8.5 Ounces
GEN 5 - EM-2 CM-2 or CM-4 4.50 Pounds 9.0 Ounces
GEN 5 - EM-2 CM-11 4.75 Pounds 9.5 Ounces
GEN 5 - EM-2 CM-3 5.00 Pounds 10.0 Ounces
GEN 5 - EM-2 CM-7 6.00 Pounds 12.0 Ounces
Table 8-3 SPLIT--SYSTEM GEN--5 WITH MICRO--CHANNEL CONDENSER
Evaporator
Condenser
Micro--Channel
Recommended
R134a Charge
Recommended
Oil Charge
E M -- 1 , E M -- 9 , I W -- 1 CM--2 3.25 Pounds 6.5 Ounces
E M -- 1 , E M -- 9 , I W -- 1 CM--3 3.75 Pounds 7.5 Ounces
E M -- 2 , I W -- 2 CM--2 3.00 Pounds 6.0 Ounces
E M -- 2 , I W -- 2 CM--3 3.50 Pounds 7.0 Ounces
E M -- 7 , I W -- 1 4 CM--2 2.75 Pounds 5.0 Ounces
E M -- 7 , I W -- 1 4 CM--3 3.00 Pounds 6.0 Ounces
EM--3 (dual loop) (2) CM --3 4.50 Pounds (each) 9.0 Ounces (each)
After determining the approximate charge using the above tables, refer to “System Performance Chart” (Table 8-5)
to determine if the correct charge has been obtained.
The data listed in Table 8-1 trough Table 8-3 is based on a 20 foot liquid line. Increase the charge by 0.5 pound for each
additional 10 feet of liquid line.
8.1.5 Evaporator Tie-In.
When an after market in-dash evaporator is added to a standard system the refrigerant charge will increase by
approximately 1 pound.
If attempting to use a CM-2 condenser with a tie-in call Carrier Transport Air conditioning technical support for an
application review.