APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
DMANDLIM
Active Demand Limit % DEM_LIM forcible
Current Running Capacity % CAPTOTAL
Demand Limit Select DMD_CTRL config
Demand Limit Switch 1 Off/On DMD_SW1 forcible
Demand Limit Switch 2 Off/On DMD_SW2 forcible
Demand Limit Sw.1 Setpt. % DLSWSP1 config
Demand Limit Sw.2 Setpt. % DLSWSP2 config
4-20 ma Demand Signal milliAmps DMDLMTMA forcible
Demand Limit at 20 ma % DMT20MA config
CCN Loadshed Signal DL_STAT
Loadshed Group Number SHED_NUM config
Loadshed Demand Delta % SHED_DEL config
Maximum Loadshed Time mins SHED_TIM config
ECON_MIN
Econ 1 Out Act.Cmd.Pos. % ECONOCMD forcible
Econ 1 Out Act.Curr.Pos. % ECONOPOS
Econ 2 Ret Act.Curr.Pos. % ECON2POS
Econ 3 Out Act.Curr.Pos. % ECON3POS
Econo Current Min. Pos. % ECMINPOS forcible
Econo Current Min. CFM CFM ECMINCFM
Outside Air CFM CFM OACFM
Diff.Air Quality in PPM DAQ
IAQ Min.Pos. Override % IAQMINOV forcible
Econ Remote 10K Pot Val. ECON_POT forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ - Discrete Input Low/High IAQIN forcible
IAQ Demand Vent Min.Pos. % IAQMINP config
Economizer Min.Position % ECONOMIN config
IAQ Demand Vent Min.Flow CFM OACFMMIN config
Economizer Min.Flow CFM OACFMMAX config
Econ.Min.Flow Deadband CFM OACFM_DB config
IAQ Analog Sensor Config IAQANCFG config
IAQ 4-20 ma Fan Config IAQANFAN config
IAQ Discrete Input Confg IAQINCFG config
IAQ Disc.In. Fan Config IAQINFAN config
IAQ Econo Override Pos. % IAQOVPOS config
Diff.Air Quality LoLimit DAQ_LOW config
Diff.Air Quality HiLimit DAQ_HIGH config
DAQ PPM Fan Off Setpoint DAQFNOFF config
DAQ PPM Fan On Setpoint DAQFNON config
Diff. AQ Responsiveness IAQREACT config
IAQ Low Reference IAQREFL config
IAQ High Reference IAQREFH config
OAQ Lockout Value OAQLOCK config
OAQ 4-20ma Sensor Config OAQANCFG config
IAQ milliamps milliAmps IAQ_MA
OAQ milliamps milliAmps OAQ_MA