90
required for ASHRAE (American Society of Heating, Refrig-
erating, and Air-Conditioning Engineers) 90.1 compliance. A
space sensor is required for non-linkage applications.
SETTING UP THE SYSTEM — The settings for tempera-
ture compensated start can be found in the local display under
Configuration
UNIT.
TCST-Cool Factor (
TCS.C) — This is the factor for the start
time bias equation for cooling.
TCST-Heat Factor (
TCS.H) — This is the factor for the start
time bias equation for heating.
NOTE: Temperature compensated start is disabled when these
factors are set to 0.
TEMPERATURE COMPENSATED START LOGIC — The
following conditions must be met for the algorithm to run:
Unit is in unoccupied state.
Next occupied time is valid.
Current time of day is valid.
Valid space temperature reading is available (sensor or
DAV-Linkage).
ITEM EXPANSION RANGE UNITS CCN POINT
TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL
TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT
Evaporator Discharge Temperature
In Subcool or Reheat Mode, compressor staging
and increased subcooling drives evaporato
r
discharge temperature down to meet higher latent
loads
A
irflo
w
EVAPORATOR
HUMIDI-MIZER ADAPTIVE
DEHUMIDIFICATION
SYSTEM COIL
Supply Air Temperature Control
Innovative algorithm to control supply air temperature
modulates flow bypass to meet desired supply air setpoint -
no overcooling or overheating of the space.
Subcooling Mode: Meet Cooling Mode Supply Air Setpoint
Reheat Mode: Meet Return Air Offset or Reheat Setpoint (configurable)
CCT
SAT
D.C.SP COOL
RAT-D.V.RA or
D.V.HT
Fig. 19 — Humidi-MiZer
®
System Control
3
4
EXPANSION
INDOOR AIR
EVAPORATOR
5
5'
EVAPORATOR
REHEAT HX
EXPANSION
DEVICE
4'
3'
CHECK VALVE
3-WAY VALVE
3a'
2'
2a'
BYPASS
MODULATING
VALVE
CONDENSER
OUTDOOR AIR
CONDENSER
MODULATING
VALVE
1'
COMPRESSOR
1
2
CONDENSER
OUTDOOR AIR
COMPRESSOR
CIRCUIT B
CIRCUIT a
Fig. 20 — Humidi-MiZer System Diagram

Table of Contents

Other manuals for Carrier WeatherExpert 48N2

Related product manuals