Table 63 — Sensor Trim Configuration
Table 64 — Switch Logic Configuration
Post Filter Status Input - Clean (
PFT.L) — The filter status
input for clean filters is set for normally open. If a field-sup-
plied filter status switch is used that is normally closed for a
clean filter, change this variable to closed.
IGC Feedback — Off (
IGC.L) — The input for IGC feed-
back is set for normally open for off. If a field-supplied IGC
feedback switch is used that is normally closed for feedback
off, change this variable to closed.
Remote Switch — Off (
RMI.L) — The remote switch is set
for normally open when off. If a field-supplied control switch
is used that is normally closed for an off signal, change this
variable to closed.
Enthaply Input — Low (
ENT.L) — The enthalpy input is set
for normally closed when low. If a field-supplied enthalpy
switch is used that is normally open when low, change this
variable to open.
Fan Status Switch — Off (
SFS.L) — The fan status switch
input is set for normally open for off. If a field-supplied fan
status switch is used that is normally closed, change this
variable to closed.
Demand Limit Switch 1 — Off (
DL1.L) — The demand
limit switch no. 1 input is set for normally open for off. If a
field-supplied demand limit switch is used that is normally
closed, change this variable to closed.
Demand Limit Switch 2 — Off (
DL2.L) — The demand
limit switch no. 2 input is set for normally open for off. If a
field-supplied demand limit switch is used that is normally
closed, change this variable to closed.
IAQ Discrete Input — Low (
IAQ.L) — The IAQ discrete in-
put is set for normally open when low. If a field-supplied IAQ
discrete input is used that is normally closed, change this vari-
able to closed.
Fire Shutdown — Off (
FSD.L) — The fire shutdown input is
set for normally open when off. If a field-supplied fire
shutdown input is used that is normally closed, change this
variable to closed.
Pressurization Switch — Off (
PRS.L) — The pressurization
input is set for normally open when off. If a field-supplied pres-
surization input is used that is normally closed, change this
variable to closed.
Evacuation Switch — Off (
EVC.L) — The evacuation input
is set for normally open when off. If a field-supplied evacua-
tion input is used that is normally closed, change this variable
to closed.
Smoke Purge — Off (
PRG.L) — The smoke purge input is
set for normally open when off. If a field-supplied smoke purge
input is used that is normally closed, change this variable to
closed.
Dehumidify Switch — Off (
DH.LG) — The dehumidify in-
put is set for normally open when off. If a field-supplied
dehumidify input is used that is normally closed, change this
variable to closed.
SF Bypass Switch — Off (
SFB.L) — The Supply Fan by-
pass switch is normally open when off. It allows operation of
the supply fan through a bypass of the supply fan VFD.
PE Bypass Switch — Off (
PEB.L) — The Power Exhaust
bypass switch is normally open when off. It allows for opera-
tion of the exhaust fan through a bypass of the exhaust fan
VFD.
Display Configuration — The DISP submenu is used
to configure the local display settings. A list is shown in
Table 65.
Test Display LEDs (
TEST) — This is used to test the opera-
tion of the ComfortLink display.
Metric Display (
METR) — This variable is used to change
the display from English units to Metric units.
Language Selection (
LANG) — This variable is used to
change the language of the ComfortLink display. At this time,
only English is available.
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim -10 - 10 ^F SAT_TRIM 0
RAT.T RAT Trim -10 - 10 ^F RAT_TRIM 0
OAT.T OAT Trim -10 - 10 ^F OAT_TRIM 0
SPT.T SPT Trim -10 - 10 ^F SPT_TRIM 0
L.SW.T Limit Switch Trim -10 - 10 ^F LSW_TRIM 0
CCT.T Air Temp Lvg Evap Trim -10 - 10 ^F CCT_TRIM 0
DTA.1 A1 Discharge Temp Trim -10 - 10 ^F DTA1TRIM 0
SP.A.T Suct.Press.Circ.A Trim -50 - 50 ^F SPA_TRIM 0
SP.B.T Suct.Press.Circ.B Trim -50 - 50 ^F SPB_TRIM 0
DP.A.T Dis.Press.Circ.A Trim -50 - 50 ^F DPA_TRIM 0
DP.B.T Dis.Press.Circ.B Trim -50 - 50 ^F DPB_TRIM 0
LP.A.T Lqd.Press.Circ.A Trim -50 - 50 ^F LPA_TRIM 0
LP.B.T Lqd.Press.Circ.B Trim -50 - 50 ^F LPB_TRIM 0
ITEM EXPANSION RANGE CCN POINT DEFAULT
SW.LG SWITCH LOGIC: NO / NC
PWS.L Power Fault Input - Good Open/Close PWRFLOGC Close
MFT.L Filter Status Input - Clean Open/Close FLTSLOGC Open
PFT.L Post Filter Stat. In-Clean Open/Close PFLTSLGC Open
IGC.L IGC Feedback - Off Open/Close GASFANLG Open
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
ENT.L Enthalpy Input - Low Open/Close ENTHLOGC Close
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
DL2.L Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open
DH.LG Dehumidify Sw. - Off Open/Close DHDISCLG Open
SFB.L SF Bypass Sw. - Off Open/Close SFBYLOGC Open
PEB.L PE Bypass Sw. - Off Open/Close PEBYLOGC Open