EasyManua.ls Logo

Carrier WeatherExpert 48N2 - Appendix E - Mode Selection; Process

Carrier WeatherExpert 48N2
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
221
APPENDIX E — MODE SELECTION PROCESS
The following section is to be used in conjunction with
Fig. 7 on page 43. To help determine why the unit controls are
in a certain mode, the programming logic is provided below.
The software will proceed, step by step, until a mode is
reached. If an “If” statement is true, then that mode will be en-
tered. The “Else” statement refers to other possible choices.
If the System Mode is OFF:
{
If the fire shut down input (Inputs
FIRE
FSD)
is in “alarm”:
HVAC mode: ("Fire Shut Down ") OFF
Else
HVAC mode: ("Disabled ") OFF
}
Else If: The rooftop is not in “factory test” and a fire
smoke-control mode is “alarming”:
{
If the pressurization input (Inputs
FIRE
PRES)
is in “alarm”:
HVAC mode: ("Pressurization ")
Else If the evacuation input (Inputs
FIRE
EVAC)
is in “alarm”:
HVAC mode: ("Evacuation ")
Else If the smoke purge input (Inputs
FIRE
PURG)
is in “alarm”:
HVAC mode: ("Smoke Purge ")
}
Else If: Someone changed the machine’s
control type (Configuration
UNIT
C.TYP) during
run time, a 15-second delay is called out:
{
HVAC mode: ("Disabled ") OFF
}
Else If: The System Mode is TEST:
{
HVAC mode: ("Test ")
}
Else If: The “soft stop” command (Service Test
S.STP)
is forced to YES:
{
HVAC mode: ("SoftStop Request")
}
Else If: The remote switch configuration (Configura-
tion
UNIT
RM.CF)=2; “start/stop”, and the remote
input state (Inputs
GEN.I
REMT)=ON:
{
HVAC mode: ("Rem. Sw. Disable") OFF
}
Else If: Configured for hydronic heat (Configuration
HEAT
HT.CF=4) or configured for dehumidification
with modulating valve reheat (Configuration
IAQ
DEHU
D.SEL=1) or configured for heat reclaim using
modulating valve (Configuration
IAQ
DEHU
H.SEL=2 and Configuration
IAQ
DEHU
D.SEL=5) and the freeze stat switch trips (Inputs
GEN.I
FRZ.S = ALRM) :
{
HVAC mode: ("Freeze Stat Trip")
}
Else If: Configured for static pressure control
(Configuration
SP
SP.CF = 1,2) and the static
pressure sensor (Pressures
AIR.P
SP) fails:
{
HVAC mode: ("Static Pres.Fail") OFF
}
Else If: Configured for supply fan status monitoring
(Configuration
UNIT
SFS.M = 1,2) and
configured to shut the unit down on fan status fail
(Configuration
UNIT
SFS.S = YES) and a fan sta-
tus failure occurs:
{
HVAC mode: ("Fan Status Fail ") OFF
Else If: Configured for return fan tracking
(Configuration
BP
BP.CF = 2) and there is a
plenum pressure switch error (Inputs
GEN.I
PP.SW=HIGH):
HVAC mode: ("Plen.Press.Fail ") OFF
}
Else If: Configured for power monitoring
(Configuration

UNIT
PW.MN) = YES and there is
a power error (Input
GEN.I
PWR.F=ALRM):>
{
HVAC mode: ("3-Phase Pwr Fail") OFF
}
Else If: There is an air pressure safety switch error
(Inputs
GEN.I

SP.SS=HIGH):
{
HVAC mode: ("Air.Pres.Sw.Fail") OFF
}
Else If: There is a VFD1 fault detected (Run Status
VFDS
S.VFD

LCF!=0) or
There is VFD1 communications failure and the supply fan
is not in bypass mode (Inputs
GEN.I
SF.BY=OFF):
{
HVAC mode: ("Supply VFD Fault") OFF
}
Else If: There is an RCB1 communications failure:
{
HVAC mode: ("RCB comm failure") OFF
}
Else If: The unit is just waking up from a power reset:
{
HVAC mode: ("Starting Up ") OFF
}
Else If: A compressor is diagnosed as being "Stuck On":
{
HVAC mode: ("Comp. Stuck On ")
}
Else: The control is free to select the normal heating/cooling
HVAC modes:
{

Table of Contents

Other manuals for Carrier WeatherExpert 48N2

Related product manuals