Table 23 — Service Test
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
TEST Service Test Mode ON/OFF MAN_CTRL
STOP Local Machine Disable YES/NO UNITSTOP
S.STP Soft Stop Request YES/NO SOFTSTOP
FAN.F Supply Fan Request YES/NO SFANFORC
INDP TEST INDEPENDENT OUTPUTS
HUM.R Humidifier Relay ON/OFF HUMR_TST
UVC.R UV-C Lamp Relay ON/OFF UVCR_TST
ALRM Remote Alarm/Aux Relay ON/OFF ALRM_TST
FANS TEST FANS
F.MO D Fan Test Automatic? YES/NO FANAUTO
E.POS Econ 1 Out Act. Cmd. Pos. 0-100 ECONFANS
SF.BY Supply Fan Bypass Relay ON/OFF SFAN_TST
S.VFD Supply Fan Commanded % 0-100 % SFVFDTST
PE.BY Power Exhaust Bypass Relay ON/OFF PEBY_TST
E.VFD Exhaust Fan Commanded % 0-100 % EFVFDTST
A.VFD MtrMaster A Commanded % 0-100 % OAVFDTST
B.VFD MtrMaster B Commanded % 0-100 % OBVFDTST
CDF.1 Condenser Fan Output 1 ON/OFF CDF1_TST
CDF.2 Condenser Fan Output 2 ON/OFF CDF2_TST
CDF.3 Condenser Fan Output 3 ON/OFF CDF3_TST
CDF.4 Condenser Fan Output 4 ON/OFF CDF4_TST
CDF.5 Condenser Fan Output 5 ON/OFF CDF5_TST
AC.T.C CALIBRATE TEST-ACTUATORS
EC1.C Econ 1 Out Act.Cmd.Pos. 0-100 ECON1TST
E1.CL Economizer Calibrate Cmd YES/NO ECONOCAL
E1C.A Econ 1 Out Act Ctl Angle CONCANG
EC2.C Econ 2 Ret Act.Cmd.Pos. 0-100 ECON2TST
E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL
E2C.A Econ 2 Ret Act Ctl Angle ECN2CANG
EC3.C Econ 3 Out Act. Cmd.Pos. 0-100 ECON2TST
E3.CL Economzr 3 Calibrate Cmd YES/NO ECON3 CAL
E3C.A Humidifier Act. Ctrl. Ang. HUMDCANG
HTC.C Ht.Coil Command Position 0-100 HTCLACTC
HT.CL Heating Coil Act. Cal.Cmd YES/NO HCOILCAL
HTC.A Heat Coil Act.Ctl.Angle HTCLCANG
HMD.C Humidifier Command Pos. 0-100 HUMD_TST
HM.CL Humidifier Act. Cal.Cmd YES/NO HUMIDCAL
HMD.A Humidifier Act.Ctrl.Ang. HUMDCANG
SRCH SEARCH FOR SERIAL NUMBER
ACTV Belimo Serial Num Search YES/NO BELSERCH
ECN.1 Economizer 1 Search EC1SERCH
ECN.2 Economizer 2 Search EC2SERCH
ECN.3 Economizer 3 Search EC3SERCH
HUMD Humidifier Valve Search UMSERCH
HT.CL Heat Coil Valve Search HTCSERCH
HMZR TEST HUMIDIMIZER
RHV Humidimizer 3-Way Valve ON/OFF RHVH_TST
C.EXV Condenser EXV Position 0-100 % CEXVHTST
B.EXV Bypass EXV Position 0-100 % BEXVHTST
C.CAL Condenser EXV Calibrate ON/OFF CEXV_CAL
B.CAL Bypass EXV Calibrate ON/OFF BEXV_CAL
EXVS
TEST CIRCUIT EXVS
A1.EX Circuit A EXV 1 Position 0-100 A_X1_TST
A2.EX Circuit A EXV 2 Position 0-100 A_X2_TST
B1.EX Circuit B EXV 1 Position 0-100 B_X1_TST
B2.EX Circuit B EXV 2 Position 0-100 B_X2_TST
A1.CL Cir A EXV 1 Calibrate ON/OFF A_X1_CAL
A2.CL Cir A EXV 2 Calibrate ON/OFF A_X2_CAL
B1.CL Cir B EXV 1 Calibrate ON/OFF B_X1_CAL
B2.CL Cir B EXV 2 Calibrate ON/OFF B_X2_CAL
COOL TEST COOLING
E.POS Econ 1 Out Act.Cmd.Pos. 0-100 % ECONCOOL
SP.SP Static Pressure Setpoint 0-5 "H2O SPSPCTST
CL.ST Requested Cool Stage 0-8 CLST_TST
MLV Minimum Load Valve Relay ON/OFF MLV_TST
A1 Compressor A1 Relay ON/OFF CMPA1TST
A1.CP Compressor A1 Capacity 20-100 A1CAPTST
A1.B1 Two Circuit Start A1,B1 ON/OFF CMPABTST
A2 Compressor A2 Relay ON/OFF CMPA2TST
A3 Compressor A3 Relay ON/OFF CMPA3TST
A4 Compressor A4 Relay ON/OFF CMPA4TST
B1 Compressor B1 Relay ON/OFF CMPB1TST
B2 Compressor B2 Relay ON/OFF CMPB2TST
B3 Compressor B3 Relay ON/OFF CMPB3TST
B4 Compressor B4 Relay ON/OFF CMPB4TST
RHV
Humidimizer 3-Way Valve ON/OFF RHVH_TST
C.EXV Condenser EXV Position 0-100 % CEXVHTST
B.EXV Bypass EXV Position 0-100 % BEXVHTST