Table 5 -- Menu Structure* (cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
{
EXPANDED PARAMETER NAME
Notes
STA TUS
(cont )
EXH1 OUT OFF ON/OFF EXHAUST ST A G E 1 RELAY OUTPUT
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
EXH2 OUT OFF ON/OFF EXHAUST ST A G E 2 RELAY OUTPUT
Out p ut of A UX term i na l; di s plays only if AUX = EXH2
ON = relay closed
OFF = relay open
MECH COOL ON 0 0, 1, or 2 Displays s t a g e of mec hanical cooling that is active.
FAN SPEED n/a LOW or HIGH SUPPLY FAN SPEED
Displays speed setting of fan on a 2- --speed fan unit.
W(HEATON) n/a ON/OFF HEAT DEMAND STATUS
Displays s tatus of heat dema nd on a 2 ---sp e e d fan unit .
SETPOINTS MAT SET 53_F
(12_C)
38 to 65_F;
(3 to 18_C)
increment by 1
SUPPLY AIR SETPO I NT
Setpoi nt determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
SeeMenuNote2.
LOW T LOCK 32_F
(0_C)
---45 to 80_F;
(---43 to 27_C)
increment by 1
COMPRESSOR LOW TEMPERA TURE LOCKOUT
Setpoi nt determines outdoor temperature when the mechanical cooling
canno t b e turned on.
DRYBLB SET 63_F
(17_C)
48 to 80_F
(9 to 27_C)
increment by 1
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoi nt determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F(17_C), unit will
economize at 62_F (16.7_C) and below and not economize at 64_F
(17.8_C) and above. There is a 2_F(1.1_C)deadband.
SeeMenuNote3
ENTH CURVE ES3 ES1, ES2, ES3, ES4, or
ES5
ENTHALPY CHANGEOVER CURVE
(Re q uires enthalpy sensor opt ion)
Enthalp y bo und a ry “curv e s for econom izing us ing single enthalp y.
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
DEMA N D CONTROLLED VENTILATION SETPOINT
Displays only if CO
2
se nsor is connected. Setpoint for Demand Cont ro lled
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
MIN POS L 6.0 V 2to10Vdc VENTILATION MINIMUM POSITION AT LOW SPEED
Displays O N LY if a CO
2
se nsor is NOT connected .
MIN POS H 4.4 V 2to10Vdc VENTILA TION MINIMUM POSITION A T HIGH SPEED
Displays O N LY if a CO
2
se nsor is NOT connected .
VENTMAX L 6.0 V 2to10Vdc DCV MA XI M UM DAMP ER P O S I TION AT LO W SP EED
(Requi res CO
2
se nsor conne cted)
VENTMAX H 4.4 V 2to10Vdc DCV MAXIMUM DAMPER POSITIO N AT HIGH SPEED
(Requi res CO
2
se nsor conne cted)
VENTMIN L 3.7 V 2to10Vdc DCV MI NIMUM DAM P ER P O S ITION AT LOW SPEED
(Requi res CO
2
se nsor conne cted)
VENTMIN H 2.8 V 2to10Vdc DCV MIN IMUM DAMP ER POSITIO N AT HI G H SPEED
(Requi res CO
2
se nsor conne cted)
EXH1 L SET 65% 0 to 100%;
Increment by 1
EXHAUST FA N ST AGE 1 SETPO INT AT LO W SPEED
Set p o int for OA d am p e r position when exhaust fan1 is p owered by the
economizer
EXH1 H SET 50% 0 to 100%;
Increment by 1
EXHA UST FA N STA G E 1 SETPOI NT A T HIGH SPEED
Set p o int for OA d am p e r position when exhaust fan1 is p owered by the
economizer
EXH2 L SET 80% 0 to 100%;
Increment by 1
EXHAUST FA N ST AGE 2 SETPO INT AT LO W SPEED
Set p o int for OA d am p e r position when exhaust fan1 is p owered by the
economizer. Only used when A UX1---O is set to EHX2.
EXH2 H SET 75% 0 to 100%;
Increment by 1
EXHA UST FA N STA G E 2 SETPOI NT A T HIGH SPEED
Set p o int for OA d am p e r position when exhaust fan1 is p owered by the
economizer. Only used when A UX1---O is set to EHX2.