38
To determine the damper setpoint position, perform the
following procedure for each condition setpoint, with
mechanical cooling OFF:
Calc ulate the appropriate supply air temperature using the
following formula:
TS = (TO x Vbz/CFM) + TR x (CFM Vbz)/CFM
TS = Supply Air Temperature
TO = Outdoor Air Temperature
Vbz = Design Maximum Ventilation CFM
CFM= Unit Supply Airflow Rate
TR = Return Air Temperature
As an example:
Unit Airfl ow Rate at High Speed is 4000 CFM
Ventilation CFM at design occupancy Vbz is 1200 CFM
TO = 60 F
TR = 75 F
Required TS = 60 x (1200/4000) + 75 x (4000 1200/4000)
=60x0.30+75x0.70=18.0+52.5
= 70.5
At t he W7220 keypa d, enter the parameter SETUP -->
VENTMAX H and adjust the setpoint value until t he
observed Supply Air Temperature (MA TEMP) reaches
70.5. Press the
“Enter” key to save this setpoint to
controller memory.
When determining VENTMIN setpoints, substitute the
value for Va in place of Vbz in the formula.
DCV Setpoint: The SETPOINTS parameter DCV SET
define s the space CO
2
leve l above which the DCV mode
begins t o open the outside air damper beyond its
VENTMIN ventilation lower limit. This setpoint should
be a minimum of 100 ppm greater than the outdoor
ambient CO
2
leve l to ensure the outside air will be
capable of diluting the space CO
2
leve l. A typical value
for outdoor CO
2
is 400 ppm; adjust the setpoint DCV SET
to 500 ppm if outdoor CO
2
leve l is not known. The
fact ory defa ult value for DCV SET is 1100 ppm.
Economize r Occupancy Control
The 24--v signal that terminates at the W7220’s OCC
input to place the economizer control in Occupied mode
when the supply fan starts is routed through the rooftop
unit’s Integrated Staging Control Board at its
OCCUPANCY jumper. To implement an occupancy
control for the economizer operation, connect a contact
set at ISC OCCUPANCY quick--connect terminals and cut
jumper JMP1. To allow automatic occupancy mode, close
the control contacts. To place the economizer in
Unoccupie d mode , open the control contact s.
CUT JUMPER JMP1
TO IMPLEMENT
OCCUPANCY
CONTROL
OCCUPANCY
TERMINALS
C13674
Fig. 51 -- Integrated Staging Control Board (ISC) -- Occ upancy Terminals and Jumper