Hardware
Actuators —
The EconoMi$er
R
X damper actuators are direc t--coupled
types with spring--return. Power is 24--v from the W7220
outputs. Range of rotation is 95--degrees; timing for
full--range movement is 90 seconds to drive open in
normal operation, 30 seconds in Test Mode and 25
seconds for spring return.
These actuators are S --bus enabled. The S --bus is a
proprietary local equipment network that connects the
W7220 c ontroller, one S--enabled actuat or and up to three
S--type enthalpy sensors on a two--wire communi cation
network. The S--bus is polarity--insensitive. Devices
attached to the S--bus are automatica lly recognized by the
controller.
Actuator command position is defined in a 2 --10 vdc
value. 2.0--v is outside air damper position fully--closed
(0% open); 10.0--v is damper position fully--open (100%
open). See Table 9 to correlate control voltage values to
outside air damper opening percentage.
Table 9 – Actuator Voltage vs. Damper Position
Vdc %Open Vdc %Open Vdc %Open
2.0 0 4.8 35 7.6 70
2.4 5 5.2 40 8.0 75
2.8 10 5.6 45 8.4 80
3.2 15 6.0 50 8.8 85
3.6 20 6.4 55 9.2 90
4.0 25 6.8 60 9.6 95
4.4 30 7.2 65 10.0 100
These units use a 3--Nm (27 lb--in.) torque m odel,
Honeywell Series MS3103K actuator.
Supply Air Temperature Sensor —
The W7220 controller uses a 20--k ohm analog sensor for
Supply Air Temperature (SAT). The therm istor is attached
to a ring terminal. The ring terminal is attached to the
unit’s supply fan housing, downstream of the unit’s indoor
coil. The SAT sensor is connect ed to the W7220 input
terminals marked MAT. See Tabl e 10 for sensor resistance
to temperature correlations.
The W7220 controller requi res a valid signal from its SAT
channe l in order to function. If the SAT connection t o the
W7220 is lost, the W7220 will initiate an alarm c ondition
immediately. No economizing operation will be permitted
until this alarm is cleared.
Table 10 – SAT/OAT Sens o r Chara cteris t ics
Deg C Ohms Deg F Ohms
--- 3 0 415156 --- 2 0 386130
--- 2 5 301540 0 193070
--- 2 0 221210 20 101820
--- 1 5 163834 32 70200
--- 1 0 122453 40 55420
--- 5 92382 45 47771
0 70200 50 41258
5 53806 55 35725
10 41561 60 31035
15 32341 65 27069
20 25346 70 23719
25 20000 77 20000
30 15886 80 18473
35 12698 100 11544
40 10212 120 6768
45 8261
50 6720
Outside Air Temperature Sensor —
EconoMi$e r X systems equipped with outdoor dry bulb
temperature changeover control include a 20--k ohm
analog sensor to measure Outdoor Air Temperature
(OAT). This is the same sensor used for the SAT function;
see Table 10 for resistance vs temperature characteristics.
The OAT sensor is attached to the outside air damper frame.
It is connected to the W7220’ s OAT input terminals.
If an access ory enthalpy sensor is added to an EconoMi$er
X system with factory dry bulb changeover, disconnect this
OAT sensor wiring at the W7220’ s OAT input terminals.
Enthalpy Control Sensor Configuration—
The W7220 economizer control system can accommodate
up t o t hree S--bus enthalpy sensors. On EconoMi$er X
models with factory--installed Enthalpy Changeover
control, one S--bus sensor is provided in the economizer
outdoor section. Additional sensors may be added to
measure Ret urn Air and Discharge Air conditions.
The Enthalpy Control sensor (Part Number: HH57AC081)
communicates with the W7220 Economizer controller on the
two--wire local equipment network bus (S--bus) and can
either be wired using a two--pin header or using a side
connector . This sensor is used for all OAT (Outdoor Air
Temperature), RAT (Return Air Temperatu re) and DAT
(Discharge Air Temperature), depending on how its three
pos itio n DIP switch is set.
Use Fig. 52 and Table 11 to locate the wiring terminals for
each Enthalp y Contro l senso r.
Us e Fig . 52 and Table 12 to set the DIP switches for the
desired use (location) of the sensor .