Table 5 -- Menu Structure* (cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
{
EXPANDED PARAMETER NAME
Notes
CHECKOUT DAMPER VMIN .HS n/a n/a P ositions OA damper to VMIN High Speed position
DAMPER VMAX .HS n/a n/a Positions OA damper to VMAX High Speed position
DAMPER OPEN n/a n/a P osi t ions OA damper to the full open posi ti on.
DAMPER CLOSE n/a n/a Pos it i ons damper to the fully closed posi ti on
CONNECT Y1---O n/a n/a Cl ose s t he Y1 --- O r el a y ( Y1 --- O)
CONNECT Y2---O n/a n/a Cl ose s t he Y2 --- O r el a y ( Y2 --- O)
CONNECT AUX1O n/a n/a Energi z e s the AU X1O output. If Aux s etting is:
S NONE --- not action taken
S ERV --- 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are good for ERV operation.
{{
S S YS --- 2 4 V a c o u t . I ss u e s a s y s t e m a l a r m
ALARMS(_) Ala rm s d ispla y only when they are act ive. The menu ti t le “ALARMS(_) ”
includes the number of acti ve alarms in parenthesi s ( ).
MA T SENS ERR n/a n/a SUPPLY AIR TEMPER ATURE SENSO R ERRO R
CO2 SENS ERR n/a n/a CO2 SENSOR ERROR
OA T SENS ERR n/a n/a OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OA SYLK SENS ERR n/a n/a OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected on S---bus
DA T SENS ERR n/a n/a DISCHARGE AIR TEMPERA TURE SENSOR ERROR
SYS ALARM n/a n/a When AUX is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX terminal has 24 Vac out.
ACT UNDER V n/a n/a ACTUATOR VOL TAGE LOW
Voltag e received at actuator is below expected range
ACT OVER V n/a n/a ACTUATOR VOLT AGE HIGH
Voltag e received at actuator is above expected range
ACT STALLED n/a n/a ACTUATOR STALLED
Act uator stopped before reaching commanded posi ti on
*
Table 5 illustrates the complete hierarchy, your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
2
) sensor, then none of the DCV parameters appear.
{
When values are displayed, pressing and holding the Y or B button causes the display to automatically increment.
**
n/a = not applicable
{{
ERV Operation: When in Cooling mode AND the conditions ar e NOT OK for economizing --- the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
Menu Notes
1 S T A T U S --- > O C C U P I E D – The factory-standard Occupancy signal originates with a thermostat or other controller call for indoor fan operation at ISC termi-
nal G. This signal passes through the Integrated Staging Control Board’s OCCUPIED jumper JMP1 to the ECONO conn ector and to th e W7220’s OCC input
terminal. An external timeclock or relay is required to implement an Occupancy schedule on the economizer damper position.
2 STA TUS -> MA TEMP, SETPOINTS -> MAT SET – Th e W7220 menu parameters and labels include designa tions MA, MAT and Mixed Air for the economizer
cooling control sensor. On these rooftop units, the economizer control sensor is located downstream of the evaporator/indoor coil in the supply fan section
where this sensor is designated as Supply Air Temperature (SAT) sensor.
3 SETPOINTS -> DRYBLB SET – This point is not displayed if a Return Air (differential) temperature sensor or an Outdoor Air enthalpy sensor is connected.
4 SYSTEM SETUP parameters must be configured as noted for 2-Speed unit operation:
EQUIPMENT =CONV
AUX2 I =W
FAN TYPE = 2SPEED