35
SYSTEM SETUP
(cont)
OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24 vac is 
input “INPUT” to the OCC terminal. If no occupancy output from the thermo-
stat then change program to “ALWAYS” OR add a jumper from terminal R to 
OCC terminal.
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD 
will 
briefly 
flash YES and change to NO but all parameters will change to the factory 
default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.
ADVANCED 
SETUP
MA LO SET 45
°
F 35 to 55
 
F; 
Incremented by 1
0
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if tem-
perature falls below setup value).
FREEZE POS CLO CLO or MIN FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;        
Increment by 10
CO
2
 ppm level to match CO
2
 sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm; 
Increment by 10
CO
2
 ppm span to match CO
2
 sensor.
STG3 DLY 2.0h 0 min, 5 min, 15 min, 
then 15 min intervals. 
Up to 4 hrs or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 cool has been active. Turns on second
 
stage of cooling 
when economizer is first
 
stage and mechanical cooling is second
 
stage. 
Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling
SD DMPR POS CLO CLO or OPN Indicates shutdown signal from space thermostat or unitary controller. When 
controller receives 24 Vac input on the SD terminal in conventional mode, 
the OA damper will open if programmed for OPN and OA damper will close if 
programmed for CLO. All other controls, e.g., fans, etc. will shut off.
DA LO ALM 45 F (7 C) 35 to 65 F; (2 to   
18 C) Incremented 
by 5 deg.
Used for alarm for when the DA air temperature is too low. Set lower range 
of alarm, below this temperature the alarm will show on the display.
DA HI ALM 80 F (27 C) 70 to 180 F; (21 to  
82 C) Incremented 
by 5 deg.
Used for alarm for when the DA air temperature is too high. Set upper range 
of alarm, above this temperature the alarm will show on the display.
DCVCAL ENA MAN MAN (manual) AUTO Turns on the DCV automatic control of the dampers. Resets ventilation 
based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and 
MA sensors.
MAT T CAL 0.0
°
F±2.5
 
F SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sensor.
OAS T CAL 0.0
°
F±2.5
 
F OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sensor.
OA H CAL 0% RH ±10% RH OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
RA T CAL 0.0
°
F±2.5
 
F RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sensor.
RA H CAL 0% RH ±10% RH RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
DA T CAL 0.0
°
F±2.5
 
F DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sensor.
2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 
minute increments
TIME DELAY ON SECOND STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to 
satisfy the call for second stage cooling before the first stage mechanical 
cooling is enabled.
CHECKOUT
DAMPER MINIMUM POSI-
TION
N/A N/A The checkout for the damper minimum position is based on the system.
DAMPER OPEN N/A N/A Position damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you 
pause in the mode to allow exhaust 
contacts to energize due to the delay in the system.
DAMPER CLOSE N/A N/A Positions damper to the fully closed position
CONNECT Y1–O N/A N/A Closes the Y1-O relay (Y1-O)
CONNECT Y2–O N/A N/A Closes the Y2-O relay (Y2-O)
CONNECT AUX1-O N/A N/A Energizes the AUX output. If Aux setting is:
•  NONE — not action taken
•  ERV — 24 Vac out. Turns on or signals an ERV that the conditions are not 
good for economizing but are for ERV operation.
††
•  SYS — 24 Vac out. Issues a system alarm
CONNECT EXH1 N/A N/A Closes the power exhaust fan 2 relay (EXH1)
Table 11 — Menu Structure* (cont)
 MENU PARAMETER
PARAMETER 
DEFAULT 
VALUE
PARAMETER 
RANGE AND 
INCREMENT
†
NOTES