43
Fig. 59 — Conduit into Control Box (Size 16)
Fig. 60 — Conduit into Single Point Box (Size 16)
Fig. 61 — Mounting Position for Field Disconnects
(over 100A) (Size 16)
Fig. 62 — Mounting Position for Field Disconnects
(up to 100A) (Size 16)
Field power wires are connected to the unit at line-side pres-
sure lugs at the main terminal block (TB1) or at factory-
installed option non-fused disconnect switch. Max wire size is
#2 AWG (copper only). See Fig. 63.
Fig. 63 — Power Wiring Connections (Size 16)
NOTE: TEST LEADS - Unit may be equipped with short leads
(pigtails) on the field line connection points off the optional dis-
connect switch. These leads are for factory run-test purposes only;
remove and discard before connecting field power wires to unit
connection points. Make field power connections directly to line
connection pressure lugs only.
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
11 12 13
L1
L2 L3
TB1
208/230-3-60
460-3-60
575-3-60
Disconnect
per
NEC