Electrical Wiring
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Denition principles of code switches:
SW01 is used to set the capabilities of the master and slave indoor units as well as the indoor unit; SW03 is used to set
the address of the indoor unit (combine original communication address and address of centralized controller).
(A) Denition and description of SW01
Note : A wired controller can connect to at most sixteen ultrathin air-duct indoor units.
Dipswitch setting
SW01_1
SW01_2
SW01_3
SW01_4
Address of
wire
controlled
indoor unit
(group
address)
[1] [2] [3] [4] Address of wire controlled indoor unit (group
address)
0 0 0 0 0# (wire-controlled master unit) (default)
0 0 0 1 1# (wire-controlled slave unit)
0 0 1 0 2# (wire-controlled slave unit)
0 0 1 1 3# (wire-controlled slave unit)
... ... .. . .. .
1 1 1 1 15# (wire-controlled slave unit)
SW01_5
SW01_6
SW01_7
SW01_8
Capability of
indoor unit
[5] [6] [7] [8] Capability of indoor unit
0 0 0 0 0.6HP
0 0 0 1 0.8HP
0 0 1 0 1.0HP
0 0 1 1 1.2HP
0 1 0 0 1.5HP
0 1 0 1 1.7HP
0 1 1 0 2.0HP
0 1 1 1 2.5HP
1 0 0 0 3.0HP
1 0 0 1 3.2HP
1 0 1 0 4.0HP
1 0 1 1 5.0HP
1 1 0 0 6.0HP
1 1 0 1 8.0HP
1 1 1 0 10.0HP
1 1 1 1 15.0HP