22 
Installation manual 
90 
64 
70 
95 
70 
95 
70 
95 
90 
110 
90 
110 
90 
110 
90 
110 
90 
110 
44 
46 
48 
50 
52 
54 
56 
58 
60 
62 
64 
Total HP  <20m  <50m 
8 10 16 
10 16 
10 16 
16 25 
16 25 
16 25 
16 25 
16 25 
25 35 
25 35 
25 35 
35 50 
35 50 
35 50 
35 50 
35 50 
35 50 
50 70 
50 70 
50 70 
50 70 
10 
12 
14 
16 
18 
20 
22 
24 
26 
28 
30 
32 
34 
36 
38 
40 
42 
Table.6-4 
Select the capacity of manual switch and fuse of the branch 
box.
See the following table. When there are no power facilities, it 
depends on the outdoor unit it connects to.
See table.6-4 below. When there is power, it depends on total 
horsepower.
Indoor power supply 
Indoor power 
Leakage protector 
Manual switch 
Branch box 
Indoor unit 
Fig.6-7 
Set the refrigerant piping system, signal wires between 
indoor-indoor unit, and those between the outdoor-outdoor 
unit into one system.
Unify the power supply to all indoor units in the same 
system.
Do not put the signal wire and power wire in the same wire 
tube; keep some distance between the two tubes. (Current 
capacity of the power supply: less than 10A--300mm, less 
than 50A--500mm.)
Set the address of the outdoor unit in case there are parallel 
multi-outdoor units.
CAUTION 
1 
9 
2 
10 
3 
11 
4 
12 
5 
13 
6 
14 
7 
15 
8 
16 
Table.6-5 
Total horsepower, capacity of manual switch and fuse
Total (HP) 
   Manual switch (A) 
Fuse(A) 
8~12 
14 
18 
20~22 
24~28 
30~34 
32 
40 
50 
63 
80 
100 
25 
35 
16 
40 
35 
40 
50 
70 
80 
Total (HP) 
   Manual switch (A) 
Fuse(A) 
36~40 
42~44 
 
125 
125 
 
100 
100 
46~50 
52~60 
62~88 
150 
200 
250 
125 
150 
200 
 
90 
110 
66 
90 
110 
68 
90 
110 
70 
90 110 72 
90 110 76 
90 110 74 
90 110 78 
90 110 80 
90 110 82 
90 110 84 
90 110 86 
90 
110 
88