24 
Installation manual 
Fig.7-1 
Fully turn on the air pipe stop valve, liquid pipe stop valve, oil 
balance valve, and air balance valve. If the above valves are 
not turned on fully, the unit will be damaged.
Check whether the power phase sequence of outdoor unit is 
correct.
All dial switches for indoor and outdoor units are set according 
to the Technical Requirements of the Product.
7.3    Fill the name of connected system 
To clearly identify the connected systems between two or 
more indoor units and the outdoor unit, select names for 
every system, and record them on the nameplate on the 
outdoor electric control box cover.
Model(indoor unit) 
Room Name e.g., indoor 
unit (A) of the first system 
on second floor is recorded 
as:-2F-1A
Outdoor unit(master unit) 
Outdoor unit(slave unit)  Outdoor unit(slave unit) 
Signal wire between indoor/outdoor units
Signal wire between outdoor units 
Indoor unit 
Indoor unit 
Indoor unit 
Signal wire between indoor units 
Signal wire between indoor unit and wire controller 
B  C  N A  P  Q  E E H2 H1 
L  N  E Q P 
B  C  N A  P  Q  E E H2 H1  B  C  N A  P  Q  E E H2 H1 
C  D  E B A  L  N  E  C  D  E B A  L  N  E  C  D  E B A Q P  Q P 
B  C  N A 
C  D  E B A  C  D  E B A  C  D  E B A 
Branch Box 
Branch Box 
L2
L3
N
L1
Power(380-415V  3N
~
 50Hz/60Hz)
Branch Box  Branch Box 
Wire controller  Wire controller  Wire controller 
Fig.6-11 
Check that the refrigeration pipe line and communication 
wire between the indoor and outdoor units are connected 
to the same refrigeration system or faults will occur.
Power voltage is within ±10% of the rated voltage.
Check that the power wire and control wire are correctly 
connected.
Check that the wire controller is properly connected.
Before powering on, confirm there is no short circuit on 
each line. 
Check whether all units have passed a nitrogen pressure 
test for 24 hours with R410A: 40 kg/cm
2
.
Confirm whether system debugging has been carried out 
for vacuum drying and packed with refrigeration as 
required.
Calculating the additional refrigerant quantity for each set 
of units according to the actual length of the liquid pipe.
Keep the required refrigerant ready.
Keep the system plan, system piping diagram, and control 
wiring diagram handy.
Record the setting address code on the system plan.
Turn on the power switches for outdoor units in advance, 
and keep them connected for at least 12 hours, so that the 
heater heats up the refrigerant oil in compressor.
6.8    Example for power wire connection 
7.1    Inspection and confirmation before 
         commissioning  
7.2    Preparation before debugging 
7.    TRIAL RUN 
Table.7-1
Factory charge / kg tonnes CO2 equivalent
Model
8,10HP
12HP
9.00
11.00
22.97
14,16,18HP
13.00
27.14
20,22HP 16.00
33.41
18.79
This product has the fluorinated gas which is listed in kyoto 
protocol it is forbidden to release to air. 
Refrigerant type: R410A,volume of GWP: 2088,
GWP=Global Warming Potential
7.4   Important information for the used 
        refrigerant
Attention:
Frequency of Refrigerant Leak Checks.
1) For equipment that contains fluorinated greenhouse gases in 
quantities of 5 tonnes of CO
2 equivalent or more,but of less 
than 50 tonnes of CO
2 equipment,at least every 12 monthes,or 
where a leakage detection system is installed, at least every 24 
monthes.
2) For equipment that contains fluorinated greenhouse gases in 
quantities of 50 tonnes of CO2 equivalent or more,but of less 
than 500 tonnes of CO2 equipment,at least every six monthes, 
or where a leakage detection system is installed, at least every 
12 monthes. 
3) For equipment that contains fluorinated greenhouse gases in 
quantities of 500 tonnes of CO2 equivalent or more,at least 
every three monthes ,or  where a leakage detection system is 
installed, at least every six monthes. 
4) Non-hermetically sealed equipment charged with fluorinated 
greenhouse gases shall only be sold to the end user where 
evidence is provide that the installation is to be carried out by 
an undertaking certified person.
5) Only certificated person is allowed to do installation, operation 
and maintenance.