Programming specific applications
ZS Sensor CARRIER CORPORATION ©2020
Applications Guide All rights reserved
24
4 Do not check a
Show on
screen. and display on the Home screen when active.
5 Configure the logic going to the MSV microblock so that it generates a
2
when the unit is in heating mode to
display
, and
3
when the unit is in cooling mode to display . When the logic generates
1
or
4
, neither
icon displays.
ZS Pro-F: To program manual HVAC control (fan only, cooling only, or heating only) using the
button
NOTE
The ZS Pro-F's button works only when the zone is occupied (green LED is on).
To program the sensor's button:
1 From the
Sys In
microblock menu, add a
BACnet Multi-State Value Parameter
microblock.
2 On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3 Select the
Zone Mode Request (601)
from the
Rnet Tag
drop-down list.
4 Check
Editable
.
5 On the
Properties
tab in the
Rnet Text
fields, type the text that you want a sensor to show for each mode.
NOTES
The letters K, M, Q, W, X do not display on a screen.
If you do not enter text, the sensor will show the Value number for the mode.