To use values from individual sensors in your control program
ZS Sensor CARRIER CORPORATION ©2020
Applications Guide All rights reserved
30
NOTES
To retrieve the temperature from a ZS duct sensor, use an ASVI microblock with the
Rnet tag
set to
Zone
Temp
.
By default, the microblock's
Display Name
and
Reference Name
are based on the Rnet tag, but you can
change these if you want. In this example, the Display Name has been changed to
Temperature
.
3 In the ANI microblock, enter the
Address
in the following format, but leave out the ASVI object name. See
example of address in the image below.