EasyManua.ls Logo

Carrier ZS Pro-F - To Wire and Mount the Switch;Sensor

Carrier ZS Pro-F
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enthalpy switch/receiver and Enthalpy sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
65
To wire and mount the switch/sensor
For Outdoor Enthalpy Control
1 To mount the enthalpy switch/receiver, insert 2 field-supplied 8 x 3/4-in. TEK screws through its side holes.
2 Remove the 4 screws holding the cover on, then remove cover.
3 Set the M1 to M3 jumper to M2. Leave the other jumper on Off.
4 Replace the cover and the 4 screws.
5 Connect the GND and 24 Vac terminals on the enthalpy switch/receiver to the controller's power terminals.
6 Connect the HI or LOW terminals on the enthalpy switch/receiver to the controller's J2-6 input.
Downloaded from ManualsNet.com search engine

Table of Contents

Other manuals for Carrier ZS Pro-F

Related product manuals