Creating Snap control programs for ZS Sensors
   
 
 
 
ZS Sensor    CARRIER CORPORATION ©2020  
Applications Guide    All rights reserved 
  9 
 
Step 3:  Add Binary Sensed Value Input microblocks if using ZS Pro 
motion sensor 
From the 
 microblock menu, add one 
 Binary Sensed Value Input
 (
) microblock that will read a 
binary value from up to 5 ZS motion sensors, and makes the value available to the control program on an output 
wire. If the Rnet has more than one ZS motion sensor, the microblock's combination algorithm determines 
whether the output value is based on a single sensor or all sensors having the same value. 
 
 
 
All values from a ZS Sensor must have an Rnet tag that defines what type of 
information this microblock's value represents. 
 If the Rnet tag droplist does not have the tag you want, you can create 
a custom tag in Snap.
 
  The Index number corresponds to the ZS sensors defined in the Sensor 
Binder microblock. Check 
for each sensor that you want to include in 
the combination algorithm used to determine the output value of the 
microblock.
 
  If using more than 1 sensor, select how the enabled sensors' values are to 
be combined to determine the microblock's output value. Select: 
 to output 1 if all sensors have a value of 1, otherwise output 0 
 to 
output 1 if any sensor has a value of 1, otherwise output 0
 
  Select 
 to have each enabled ZS Pro or Pro-F sensor display its 
individual sensed value, or 
 to have each ZS sensor display 
the value determined by the 
.  
 
 
Check the ZS Pro or Pro-F sensor screen(s) that you want this microblock's 
value displayed on.  
  Enter the text that the ZS sensor's display will show with the microblock's 
output is off or false (inactive) or when it is on or true (active). 
  The 
 your system displays when the microblock's output is off, or 
false.
 
  The 
your system displays when the microblock's output is on, or 
true.