CEL-MAR ADA-401WP - FUNCTION 0 X03; 0 X04 - READOUT of SUNLIGHT from MEASURING CHANNEL [4 X; 3 X-REFERENCES]; FUNCTION 0 X03; 0 X04 - READOUT of TEMPERATURE SET in TEMPERATURE ADJUSTER from MEASURING CHANNEL [4 X; 3 X-REFERENCES]; FUNCTION 0 X03; 0 X04 - READOUT of PERCENTAGE VALUE SET in PERCENT ADJUSTER from MEASURING CHANNEL [4 X; 3 X-REFERENCES]; FUNCTION 0 X03; 0 X04 - READOUT of CO2 CONCENTRATION MEASURING CHANNEL [4 X; 3 X-REFERENCES]

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of lighting are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of lighting in percent % (0 100 [%Lux]) is obtained from readout register according to algorithm from paragraph
7.3.1.1 by use appropriate factor value DW=10 (table p.7.3.1.1).
7.3.1.5. FUNCTION 0x03 / 0x04 – READOUT OF SUNLIGHT FROM MEASURING CHANNEL [4X
/ 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of sunlight are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of sunlight in percent % (0 100 [%SLux]) is obtained from readout register according to algorithm from paragraph
7.3.1.1 by use appropriate factor value DW=100 (table p.7.3.1.1).
7.3.1.6. FUNCTION 0x03 / 0X04 – READOUT OF TEMPERATURE SET IN TEMPERATURE
ADJUSTER FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with value of temperature set by the adjuster are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of temperature set by the use of temperature adjuster in °C (5 40 [TA(°C)]) is obtained from readout register
according to algorithm from paragraph 7.3.1.1 by use appropriate factor value DW=10 (table p.7.3.1.1).
7.3.1.7. FUNCTION 0x03 / 0X04 READOUT OF PERCENTAGE VALUE SET IN PERCENT
ADJUSTER FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with percent value set by the adjuster are in the format of 16-bit signed integer (C/C++ type short int).
The actual value set in percent adjuster in percent % (0 – 100 [PA(%)]) is obtained from readout register according to algorithm from
paragraph 7.3.1.1 by use appropriate factor value DW=10 (table p.7.3.1.1).
7.3.1.8. FUNCTION 0x03 / 0x04 – READOUT OF CO2 CONCENTRATION MEASURING
CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of CO2 concentration are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of CO2 concentration in ppm (350 – 10000 [ppm]) is obtained from readout register according to algorithm from
paragraph 7.3.1.1 by use appropriate factor value DW=1 (table p.7.3.1.1).
7.3.1.9. FUNCTION 0x03 / 0x04 – READOUT OF TEMPERATURE VALUE OF SENSOR PT100 ,
PT500, PT1000 FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-PT transducer).
The measurement value from measuring channel (DES-216-PT transducer) is presented by a 16-bit register.
The registers with measurement value of temperature from transducer PT100, PT500, PT1000 are in the format of 16-bit signed
integer (C/C++ type short int).
The actual value of measurement value of temperature from DES-216-PT transducer in °C (-200 – +600 [°C PT100] is obtained from
readout register according to algorithm from paragraph 7.3.1.1 by use appropriate factor value DW=10 (table p.7.3.1.1).
7.3.1.10. FUNCTION 0x03 / 0x04 – READOUT OF VOLTAGE VALUES 0-10V DC FROM
MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-U transducer).
The measurement value from measuring channel (DES-216-U transducer) is presented by a 16-bit register.
The registers with measurement voltage values from DES-216-U transducer, are in the format of 16-bit signed integer (C/C++ type
short int).
The actual value of measurement value of voltage from DES-216-U transducer in VDC (0 – 10 [V U10] is obtained from readout
register according to algorithm from paragraph 7.3.1.1 by use appropriate factor value DW=100 (table p.7.3.1.1).
7.3.1.11. FUNCTION 0x03 / 0x04 – READOUT OF AMPERAGE VALUES 0-20mA DC FROM
MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-I transducer).
The measurement value from measuring channel (DES-216-I transducer) is presented by a 16-bit register.
The registers with measurement amperage values from DES-216-I transducer, are in the format of 16-bit signed integer (C/C++ type
short int).