A maximum number of siren timer triggering equal with “swinger shutdown counter” established in [041] section, if zone restore event is set to occur upon
bell cut-off; please note that in this case, if the “report only first zone alarm” option is disabled, too, such a zone may record more alarms than “swinger shutdown
counter”.
Note: By default this attribute is disabled for all 1 to 12/16 zones.
Attribute 5:
When a zone allows forced arming, it will allow system/partition arming although the zone is being violated at the very moment of arming (i.e. the system can be armed even
though the PIR detector nearby the keypad detects movement when arming).
Note: By default this attribute is disabled for all 1 to 12/16 zones.
Attribute 6:
When a zone has the “chime” attribute enabled, then while the system is disarmed and the “chime” feature was activated previously by the command [*][6], any “opening” of
the zone will make the keypad buzzer to sound for 6 warning beeps.
Note: By default this attribute is enabled only for zone 1.
Attribute 7:
When a zone has the “stay” attribute enabled, then it is an interior zone and will be automatically bypassed by the system during home arming (“stay arming” or “instant stay
arming” modes).
Note: By default this attribute is set such as all 1 to 12/16 zones to be perimeter type.
Attribute 8:
ZONE SPEED: The zone speed applies to all zones whether the system is armed or disarmed. The zone speed defines how quickly the control panel will respond to an open
zone. The control panel will not display and/or respond to an open zone until the programmed zone speed elapses. All other zone definitions and options do not come into
effect until the zone speed has elapsed. The zone speed can be set either 50ms (fast detection) or 300ms (slow detection). This feature prevents any momentary glitches in
the system from causing an alarm or unnecessary reporting.
Note: By default this attribute is set such as the detection speed to be set as slow for all 1 to 12/16 zones.
After the ATTRIBUTES
1
set for selected zone was established to the required values, press [#] key to confirm.
After [#] key was pressed, the keypad buzzer will sound 3 confirmation beeps and the panel will pass to the next step.
By [#] key pressing, ATTRIBUTES
2
set can be maintained as it was previously established.
1.3 The second set of zone attributes are detailed in the table below. In order to establish the ATTRIBUTES
2
set, you should press 1 to 8 keys.
After each key pressing the appropriate attribute is enabled or disabled
2
nd
Set of attributes
Key pressed
to toggle
attribute
KP-126Pz / KP-164Pz (LED keypads) KP16LCD / KP16LCDL (LCD keypads)
Zone
LED
ON OFF
1
st
line message
2
nd
line message
Enabled Disabled
[1] 1
Enable intellizone
*
Disable intellizone
Intellizone Zxx Enable k1 Disable k1
[2] 2
Enable “sensor under test”
*
Disable “sensor under test”
Under test Zxx Enable k2 Disable k2
[3] 3
*
Enable NC contacts Enable NO contacts
ContactsType Zxx NC k3 NO k3
[4] 4
Enable tamper recognition
*
Disable tamper recognition
TamperRecogn. Zxx Enable k4 Disable k4
[5] 5
*
Enable EOL Disable EOL
EOL Zxx Enable k5 Disable k5
[6] 6
Enable ATZ
*
Disable ATZ
Zdoubling Zxx Enable k6 Disable k6
[7] 7
ATZ parallel wiring
*
ATZ series wiring
ATZ wiring Zxx parallel k7 series k7
All the second set of attributes is presented below: