BLP / BL
Y
HEAT PUMP
19
F40 Water Pump Select 0 1 1 -
0: water pump is not enable
1: water pump is enable
F41
Water pump starts time
before compressor starts
1 10 3 min
F42
Water pump stops time
after compressor stops
0 10 3 min
F43 Water pump stop time
OFF
1 99
60 min
Water Pump
F44 Water pump run time
OFF
1 10
5 min
F50 External alarm mode 0 -- 4 3 -
0: without external alarm
1: always open, unlocked
2: always open, locked
3: always closed, unlocked
4: always closed, locked
Alarm
F59
Buzzer alarm sound
duration
OFF,
0.1 -- 10,
On
OFF min
Off: No alarm sound
On: Alarm sound is always
on until pressing any key
F60 Set the RTC time 00:0023:59 - -
F61 Period 1 start time
00:0023:59
OFF
0500 -
F62 Period 1 end time
00:0023:59
OFF
0700 -
F63 Period 2 start time
00:0023:59
OFF
1600 -
F64 Period 2 end time
00:0023:59
OFF
1800 -
F65 Period 3 start time
00:0023:59
OFF
2200 -
F66 Period 3 end time
00:0023:59
OFF
0000 -
OFF means not using
F69 Run Mode 0/1 0 -
0Automatic
1Economical
RTC
F80 Password
OFF
0001 -- 9999
OFF -
OFF means no password
0000 means clearing
password
F81 Temperature unit C/F C -
C:
Centigrade
F: Fahrenheit
F85
Display accumulative
running time
- - hour
F86
Accumulative running
time reset
- - -
F87 Probation time
OFF
1 -- 9999
OFF hour
The controller will stop if the
accumulative time is over
probation time, and show the
alarm code A99.
OFF means no probation
time
System
setting
F98 Reserved
F99 Test self
This function can attract all relays in turn, and please dont use it
when the controller is running! Testing
End Exit