36
Defrost (only applicable to the heating mode)
1. the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil
pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not according to
conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically enters defrosting
process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board
unit start defrost shall all meet the following conditions
acompressor continuous running over 7 minutes
bdefrost relay shut off-5℃)
ccompressor cumulate running time over 50 minutes.
first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
Defrost time(minute) Next defrost interval time(minute)
15 30
10--15 40
7--10 60
3--7 70
3 80
2end defrost condition(meet one of follows)
adefrost time have fifteen minutes.
bdefrost relay turn on(>8℃)
cpress ON/OFF key in defrost process.