Water leakage of
indoor unit
The outlet part broke.
Paste new gland strip.
When bending tube of the
evaporator collides with the
PCB's wire, the condensed
water would flow along the
wire, and can't flow into the
receiving water tank.
Please avoid contacting
between the bending tube and
the PCB’s wire.
A lot of evaporator fins fall
down to lead to bad flow.
Renovate these faulty fins.
The indoor unit didn’t install
correctly according to the
requirement.
Please reinstall the indoor unit
correctly.
The damping rubber is shedding
Put again
The drain pipe is shedding
Fix again
The filter or evaporator is very
dirty
Clean it
refrigerant isnt enough,cause
the evaporator ice,leak water
after off
Refill refrigerant