E12
Item Range Default
MODE 5
Linear decimal point  :No decimal point
 :1-digit after decimal point□□to
 :4-digit after decimal point

Linear scale zero
 to □□

Linear scale span
 to

Sensor correction  to [°C] □□
Digital filter  to [sec] □□□
SV limiter L  to [°C]

SV limiter H  to [°C]

Display decimal point  :No decimal point
 :1-digit after decimal point□□to
 :4-digit after decimal point

MODE 6
Pulse cycle to [sec] □□□
Feedback zero
 to [%] □□□
Feedback span
 to [%] 
Feedback deadband
 to [%] □□□
PID deadband/
output deadband
 to [%] □□□
Control action  :Heating control
 :Cooling control

Output preset  to [%] □□
Output variation limiter L
 to [%]

Output variation limiter H
 to [%] 
PV abnormal output  to [%] □□□
Preset manual  to [%] □□□
Operation on power ON  :READY status/program operation
RESET
 :Operation right before previous
power-OFF

Control algorithm  :Position PID control
 :Velocity PID control
 :Z control

or

Feedforward :Without feedforward calculation
 :With feedforward calculation
□□
MODE 7
Output 2 control system  :PID control or Z control
 :Split control
□□
Output 2 P
:Two-position control
 to [%]
□□□
Output 2 I
t o [sec] □□□
Output 2 D
t o [sec] □□□
Output 2 gap
 to [%] □□□
Output 2
PID deadband/
output deadband
 to [%] □□□
Output 2 control action  :Heating control
 :Cooling control

Output 2 output preset
 to [%] □□□
Split Direct
 to [%] □□□
Split Reverse  to [%] 
Output 2 pulse cycle to [sec] □□□
Output 2 output limiter L
 to [%] □□□
Output 2 output limiter H
 to [%] 
Output 2 variation limiter L
 to [%]

Output 2 variation limiter H  to [%] 
Output 2 preset manual  to [%] □□□
MODE a
Communication protocol
□□ :MODBUS RTU
 :MODBUS ASCII

:Private
□□
Communication function □□ :Host communication
 :Digital transmission
 :Digital remote input
□□
Instrument No. to □□□□
Communication transmission
rate
 :4800bps  :9600bps
 :19200bps  :38400bps

Communication character :7-bit/even parity/stop bit 1
:7-bit/even parity/stop bit 2
:7-bit/odd parity/stop bit 1
:7-bit/odd parity/stop bit 2
:8-bit/no parity/stop bit 1
:8-bit/no parity/stop bit 2
:8-bit//even parity/stop bit 1
:8-bit/even parity/stop bit 2
:8-bit/odd parity/stop bit 1
:8-bit//odd parity/stop bit 2
□□
Digital transmission type  :Digital SV transmission
 :Digital PV transmission
 :Digital output 1 transmission
 :Digital output 2 transmission
 :Digital output FB transmission
□□□
Digital transmission cycle  :100msec cycle
 :200msec cycle
 :1 sec cycle

Communication display  :No communication display
 :With communication display
□□
Item Range Default
MODE b
Transmission type  :SV transmission signal output
 :PV transmission signal output
 :Output 1 transmission signal output
 :Output 2 transmission signal output
 :FB transmission signal output
□□□
Transmission scale zero  to [°C]

Transmission scale span  to [°C]

MODE c
Remote/local
switching
 :Local SV operation

:Remote SV operation

Remote SV shift  to [°C] □□
Remote SV filter  to [sec] □□□
Tracking at
switch to local
 :Function OFF
 :Tracking function ON
□□
Remote SV scale zero  to [°C]

Remote SV scale span
 to [°C]

Cascade γ
 to □□
Cascade β  to □□□
MODE d
External input 1 □□ :Function OFF
 :RUN/READY switch
 :AUTO/MANUAL switch
 :Preset manual
 :Timer 1
 :Timer 2
 :Alarm event reset
 :Execution No. selection 1 (Bit0)
 :Execution No. selection 2 (Bit1)
 :Execution No. selection 4 (Bit2)
 :Execution No. selection 8 (Bit3)
 :Program/constant value operation switch
 :Program operation RUN/STOP
 :Program operation ADVANCE
 :Program operation RESET
 :Program pattern 1 (Bit0)
 :Program pattern 2 (Bit1)
 :Program pattern 4 (Bit2)
□□
External input 2
External input 3
External input 4
External input 5
External input 6
External input 7
MODE t
Key lock □□ :No key lock
 :Operation parameter keys locked
□□ :All parameter keys locked
□□
Operation initial screen □□ :PV/SV display screen
 :PV/step time display screen
 :PV/OUT1 display screen
 :PV/OUT2 display screen
□□□
Operation screen SV display □□ :SV display
 :Blank display
 :Multi-display

Bar display □□ :No display
 :Output 1 display
 :Output 2 display
□□□ :CT measured value display
□□□ :FB measured value display
 :Step remaining/elapsed time display
□□
Parameter storing  :Backup function OFF
 :Backup function ON
□□□
Parameter initialization  :No initialization
 :Initialization executed
□□
Port switch  :USB engineering port
:IR engineering port
□□
Multi-output switch  :Normal output
 :ON-OFF pulse output
 :Analog output
□□ :SSR drive pulse output

Calculation RESET at READY  :Calculation continue
 :Calculation RESET

Anti-reset
wind up L  to□□ [%]

Anti-reset
wind up H □□□ to [%]

32-8, KUMANO-CHO, ITABASHI-KU, TOKYO 173-8632
PHONE: +81-3-3956-2171
FAX: +81-3-3956-0915
E-mail: inter@chino.co.jp
Website: https://www.chino.co.jp
July. ’21
DB6-61-6