13
Figure 6.1
Replacing Output Module
Housing
Clip
Back Cover
Controller
Pin
Module
Auto Cycle Time
The Control Output Modules have a default cycle time
of 1 second (fast switching) or 30 seconds (slow switch-
ing) (See table on page 17). After replacing a control
output, the 2110 verifies at power up if a slow or fast
cycle time output has been installed. If an output with
a different default cycle time is installed, the 2110 will
change the cycle time to the new device’s default. If the
user has changed the cycle time in configuration, the
2110 retains this value unless an output with a different
default cycle time has been installed.