NA06.130 C EN - 10
17 - TECHNICAL CHARACTERISTICS
CD 100 V 120 V 150 V 180 V 200 V 240 V 300 V
Standard version
Cooling capacity (1) kW 25.6 28.3 37 44.1 49.9 57.7 73.2
Power input (2) kW 8.7 10 13 14 17 20 27
Low-noise version
Cooling capacity (1) kW 24.3 26.7 34.4 41.6 45.6 55.7 70.2
Power input (2) kW 9.04 10.6 14.1 15.2 18.6 20.3 27.6
Compressor
Type SCROLL
Quantity 1 2
Rotation speed rpm 2900
R410A refrigerant kg - GWP Unit not loaded (nitrogen safety load) - 2088 (4)
Power control % 100-0 100-50-0
LP low
pressure circuits
Quantity 1
Circuit 1 / circuit 2 distribution % 100 / 0
Min./max. evaporation temperature °C -10 / +10
Air-cooled
condenser
Fans Direct drive axial
Number of fans/dia. mm 1 x 800
Rotation speed STANDARD VERSION: 750 rpm
Air flow rate m3/h 16700 15500 16100 24000
Qty - motor output per unit kW 1 x 0.9 1 x 1.7
Rotation speed LOW NOISE VERSION 500 rpm
Air flow rate m3/h 10800 9700 10800 18000
Qty - motor output per unit kW 1 x 0.46 1 x 1.2
Standard version Lw / Lp (3) dB(A) 80/49 81/50 86/54 88/56
Low-noise version Lw / Lp (3) dB(A) 75/44 77/46 78/47 81/49 83/51
CD 350 V 400 V 500 V 540 V 600 V 700 V
Standard version
Cooling capacity (1) kW 87.9 97.8 121 124 144 164
Power input (2) kW 29 35 42 46 53 61
Low-noise version
Cooling capacity (1) kW 85.6 93.8 116 120 138 159
Power input (2) kW 30.7 35.5 43.6 47 54.9 62.3
Compressor
Type SCROLL
Quantity 2 4
Rotation speed rpm 2900
R410A refrigerant kg - GWP Unit not loaded (nitrogen safety load) - 2088 (4)
Power control % 100-43-0 100-37-0 100-50-0 100-72-50-22-0 100-75-50-25-0 100-78-50-22-0
LP low
pressure circuits
Quantity 1 2
Circuit 1 / circuit 2 distribution % 100 / 0 50 / 50
Min./max. evaporation temperature °C -10 / +10
Air-cooled
condenser
Fans Direct drive axial
Number of fans 2 x 800
Rotation speed STANDARD VERSION: 900 rpm
Air flow rate m3/h 44000 42000 41000 44000
Qty - motor output per unit kW 2 x 1.7 2 x 1.8 2 x 1.7
Rotation speed LOW NOISE VERSION 750 rpm
Air flow rate m3/h 32000 29000 30500 35000
Qty - motor output per unit kW 2 x 1.2 2 x 1.1
Standard version Lw / Lp (3) dB(A) 89/57 90/58 91/59
Low-noise version Lw / Lp (3) dB(A) 83/51 85/83
(1) Cooling capacity for an evaporation temperature of +2°C and condenser air inlet temperature of 35°C.
(2) Power input of compressors + fans
(3) Lw: overall sound power level as per standard ISO3744
Lp: overall pressure level at 10 metres in a free eld calculated using the formula Lp=LW-10logS
(4) Users must have systems containing refrigerant periodically checked for leaks by qualied personnel. The frequency of checks
depends on the refrigerant charge.