Instruction Manual
RGU-10 B, RGU-10 B RCM
5. CONFIGURATION
5.1.- ADIRECT SETTING
By pressing for a long time on any of the direct setting buttons, Configuration mode is entered and the
relay’s setting may be changed.
While in Configuration mode if any other direct function is used (Id, td, Std/+ y Auto), the parameter
for the displayed relay can also be set.
Configuration mode is exited if no buttons are pressed for a while with the last setting being “SAVE”.
5.1.1.- SETTING THE SENSITIVITY TRIP
Pressing Id for more than one second, Configuration appears and a setting from the list is increased
with every press. The current setting is seen in small figures and the new setting in the main figures.
Figure 14: Setting the sensitivity trip.
Possible setting values are: 100 mA, 300 mA, 500 mA, 1 A, and 3 A.
5.1.2.- DELAY SETTING AND MAIN RELAY CURVE
Pressing td for more than one second, Configuration appears and a setting from the list including
curve types is increased with every press.
The current setting is seen in small figures and the new setting in the main figures.
Figure 15:Delay setting.
Possible setting values are: 100, 200, 300, 400, 500, 750 ms, 1, 5 and 10 s.