WS1 & 1.25 Man u al Page 11
OEM Filter System Setup Quick Reference
This is a quick reference setup procedure. See OEM Filter System Setup Detail for
more information on available settings.
STEP 1F – Press NEXT and ▼ simultaneously for 3 seconds. If screen in step 2F does
not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT,
▲, and SET CLOCK in sequence, then press NEXT and ▼ simultaneously for 3
seconds.
STEP 2F – Choose Filtering using ▼ or ▲. Press NEXT to go to step 3F. Press
REGEN to exit OEM Filter System Setup.
STEP 3F – Enter “oFF” if regenerant is not used (i.e. backwash only) or enter the re ll
volume (in gallons) using ▼ or ▲. Prior to selecting oFF or regenerant volume, verify the
correct valve body, main piston, regenerant piston, and stack are being used, and that the
injector or injector plug(s) are in the correct locations. See Compliance Table in Service
Instructions under Injector Cap, Screen, Injector Plug and Injector section and Figure 6.
Press NEXT to go to step 4F. Press REGEN to return to previous step.
STEP 4F – Backwash: Select using ▼ or ▲:
• “NORMAL” for one “NORMAL” backwash (14 minutes);
• “NORMAL 2” for two “NORMAL” backwashes (8 minutes each);
• “LONGER” for one “LONGER” backwash (16 minutes); or
• “LONGER 2” for two “LONGER” backwashes (12 minutes each).
See Tables 5 and 6 for additional details. Press NEXT to go to step 5F. Press REGEN
to return to previous step.
STEP 5F – Set Gallons Capacity using ▼ or ▲:
• “oFF” (regeneration based on day override); or
• number of gallons (20 to 50,000).
See Setting Options Table for more detail. Press NEXT to go to step 6F. Press REGEN
to return to previous step.
STEP 6F – Set Re ll option using ▼ or ▲:
• “PoST” to re ll the brine tank after the nal rinse; or
• “PrE” to re ll the brine tank two hours before the re gen er a tion time set.
Press NEXT to go to step 7F. Press REGEN to return to previous step.
STEP 7F – Set Regeneration Time Option using ▼ or ▲:
• “NORMAL” means regeneration will occur at the preset time;
• “on 0” means regeneration will occur immediately when the gallons capacity
reaches 0 (zero); or
• “NORMAL + on 0” means regeneration will occur at one of the following:
• the preset time when the speci ed number of days between regenerations is
reached; or
• after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
This display will not appear if Step 5F is set to oFF.
See Setting Options Table for more detail. Press NEXT to exit OEM Filter System
Setup. Press REGEN to return to previous step.
RETURN TO
NORMAL MODE
STEP 1F
STEP 2F
STEP 3F
STEP 4F
STEP 5F
STEP 6F
STEP 7F